wago 2000-2228

Selling Points

  • 1Reliable Ex e II Application: Designed for Ex e II applications, ensuring safety in hazardous environments.
  • 2Push-In Connectors: Easy to connect with push-in actuators, reducing installation time.
  • 3Copper Conductors: Compatible with copper conductors, providing excellent electrical conductivity.
  • 4Gray Polyamide Housing: Made from durable gray polyamide (PA66) for insulation and longevity.
  • 5DIN-Rail Mounting: Suitable for DIN-rail 35 x 15 and 35 x 7.5, offering versatile mounting options.
Product Details
2000-2228
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
4
Total number of potentials
2
Number of levels
2
Number of jumper slots
4
Width
3.5?mm?/ 0.138?inches
Height
69.7?mm?/ 2.744?inches
Depth from upper-edge of DIN-rail
51.7?mm?/ 2.035?inches
Potential Marking
Shield/L
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Weight
9.5g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-41
eCl@ss 9.0
27-14-11-41
ETIM 9.0
EC000901
ETIM 8.0
EC000901
ECCN
NO US CLASSIFICATION
PU (SPU)
50?pcs
Packaging type
box
Country of origin
DE
GTIN
4055143869225
Customs tariff number
85369010000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
ATEX: PTB 11 ATEX 1041 U / IECEx: PTB 11.0093U (Ex eb IIC Gb)
Rated voltage (III / 3)
500V
Rated impulse voltage (III / 3)
6kV
Rated current
13.5A
Current at conductor cross-section (max.) mm2
16A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
300V
Rated current UL (Use Group B)
15A
Rated voltage UL (Use Group C)
300V
Rated current UL (Use Group C)
15A
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
10A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
10A
Rated voltage EN (Ex e II)
350V
Rated current (Ex e II)
13A
Rated current (Ex e II) with jumper
12A
Power loss, per pole (potential)
0.868W
Rated current I<sub>N</sub> for specified power loss
13.5A
Resistance value for specified, current-dependent power loss
0.002Ω
Connection technology
Push-in CAGE CLAMP?
Total number of connection points
2
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
1 mm2
Solid conductor
0.14 … 1.5?mm2?/ 24 … 16?AWG
Solid conductor; push-in termination
0.5 … 1.5?mm2?/ 20 … 16?AWG
Fine-stranded conductor
0.14 … 1.5?mm2?/ 24 … 16?AWG
Fine-stranded conductor; with insulated ferrule
0.14 … 0.75?mm2?/ 24 … 18?AWG
Fine-stranded conductor; with ferrule; push-in termination
0.5 … 0.75?mm2?/ 20 … 18?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
9 … 11?mm?/ 0.35 … 0.43?inches
Wiring direction
Front-entry wiring
Number of connection points 2
2
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice