wago 2001-1404

Selling Points

  • 1Push-in CAGE CLAMP Technology: Easy and tool-free connection of solid core cables.
  • 2DIN Rail Mounting: Seamless integration on DIN rails for efficient power distribution.
  • 3Compliance with UL 1059 & BS7671: Meets stringent international safety standards for electrical installations.
  • 4Blue Color Coding: Visual identification of connections for enhanced safety and organization.
  • 5High Current Rating: Supports up to 18A, suitable for various industrial applications.
Product Details
2001-1404
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
4
Total number of potentials
1
Number of levels
1
Number of jumper slots
2
Width
4.2?mm?/ 0.165?inches
Height
69.9?mm?/ 2.752?inches
Depth from upper-edge of DIN-rail
32.9?mm?/ 1.295?inches
Depth
39.5 mm / 1.555 inches
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
blue
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.124MJ
Weight
5.1g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-20
eCl@ss 9.0
27-14-11-20
ETIM 9.0
EC000897
ETIM 8.0
EC000897
ECCN
NO US CLASSIFICATION
PU (SPU)
100?pcs
Packaging type
box
Country of origin
DE
GTIN
4017332998673
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
ATEX: PTB 05 ATEX 1094 U / IECEx: PTB 05.0034U (Ex eb IIC Gb)
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated current
18A
Current at conductor cross-section (max.) mm2
24A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
15A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
15A
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
15A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
15A
Reference hazardous areas
See application instructions in section “Knowledge andDownloads – Documentation – Additional Information: Technical Section; Technical Explications”
Rated voltage EN (Ex e II)
550V
Rated current (Ex e II)
17A
Rated current (Ex e II) with jumper
16A
Power loss, per pole (potential)
0.593W
Rated current I<sub>N</sub> for specified power loss
18A
Resistance value for specified, current-dependent power loss
0.002Ω
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
1.5 mm2
Solid conductor
0.25 … 2.5?mm2?/ 22 … 14?AWG
Solid conductor; push-in termination
0.75 … 2.5?mm2?/ 18 … 14?AWG
Fine-stranded conductor
0.25 … 2.5?mm2?/ 22 … 14?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 1.5?mm2?/ 22 … 16?AWG
Fine-stranded conductor; with ferrule; push-in termination
0.75 … 1.5?mm2?/ 18 … 16?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
9 … 11?mm?/ 0.35 … 0.43?inches
Wiring direction
Front-entry wiring
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice