wago 2001-408

Selling Points

  • 1High Current Rating: 18A rated current for reliable performance.
  • 2Compact Design: Dimensions of 32.3 mm x 4.1 mm x 19 mm for easy installation.
  • 3Insulated for Safety: Insulated to prevent electrical shock and ensure safety.
  • 48-Way Configuration: Ideal for cross-connection and jumper applications.
  • 5Light Gray Color: Easy to identify in industrial settings with its light gray color.
Product Details
2001-408
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
32.3?mm?/ 1.272?inches
Height
4.1?mm?/ 0.161?inches
Depth
19?mm?/ 0.748?inches
Jumper assignment
1-2-3-4-5-6-7-8
Note (material data)
Information on material specifications can be found here
Color
light gray
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.024MJ
Weight
3g
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-40
eCl@ss 9.0
27-14-11-40
ETIM 9.0
EC000489
ETIM 8.0
EC000489
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
bag
Country of origin
DE
GTIN
4055143699334
Customs tariff number
8536698000
RoHS Compliance Status
Compliant,No Exemption
Rated voltage (III / 3)
800V
Rated current
18A
Rated current (Ex e II)
16A
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice