wago 2002-1901

Selling Points

  • 1Push-in CAGE CLAMP Technology: Fast and vibration-proof connection for solid and stranded conductors.
  • 2Test Option Included: Ensures highest level of safety and compliance with industrial standards.
  • 3Additional Jumper Position: Enhances flexibility and customization options for your application.
  • 4DIN-Rail Mounting: Compatible with DIN-rail 35 x 15 and 35 x 7.5, ideal for industrial settings.
  • 5Gray Color and Gray Finish: Durable and easy-to-use design with side and center marking for clear identification.
Product Details
2002-1901
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
2
Total number of potentials
1
Number of levels
1
Number of jumper slots
3
Width
5.2?mm?/ 0.205?inches
Height
72.9?mm?/ 2.87?inches
Depth from upper-edge of DIN-rail
32.9?mm?/ 1.295?inches
Depth
39.5 mm / 1.555 inches
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.168MJ
Weight
8.4g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-20
eCl@ss 9.0
27-14-11-20
ETIM 9.0
EC000897
ETIM 8.0
EC000897
ECCN
NO US CLASSIFICATION
PU (SPU)
50?pcs
Packaging type
box
Country of origin
CN
GTIN
4055143302807
Customs tariff number
85369010000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
ATEX: KIWA 17 ATEX 0030 U / IECEx: KIWA 17.0014U (Ex ec IIC Gc)
Rated voltage (III / 3)
400V
Rated impulse voltage (III / 3)
6kV
Rated current
16A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
300V
Rated current UL (Use Group B)
15A
Rated voltage UL (Use Group C)
300V
Rated current UL (Use Group C)
15A
Rated voltage CSA (Use Group B)
300V
Rated current CSA (Use Group B)
15A
Rated voltage CSA (Use Group C)
300V
Rated current CSA (Use Group C)
15A
Reference hazardous areas
See application instructions in section “Knowledge andDownloads – Documentation – Additional Information: Technical Section; Technical Explications”
Rated voltage EN (Ex e II)
440V
Rated current (Ex e II)
17A
Power loss, per pole (potential)
0.341W
Rated current I<sub>N</sub> for specified power loss
16A
Resistance value for specified, current-dependent power loss
0.001Ω
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm2
Solid conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Solid conductor; push-in termination
0.75 … 4?mm2?/ 18 … 12?AWG
Fine-stranded conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5?mm2?/ 22 … 14?AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5?mm2?/ 18 … 14?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12?mm?/ 0.39 … 0.47?inches
Wiring direction
Front-entry wiring
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice