wago 2002-2206

Selling Points

  • 1Supports various conductor sizes (0.25mm² to 4mm²) and types.
  • 2Made from Polyamide (PA66) for high durability and resistance to environmental factors.
  • 3Push-in CAGE CLAMP connections ensure secure and efficient wire installation.
  • 4Meets IEC, EN, CSA, and UL standards for safety and performance.
  • 5Suitable for DIN-rail 35 x 15 and 35 x 7.5 with a compact design.
Product Details
2002-2206
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
4
Total number of potentials
2
Number of levels
2
Number of jumper slots
4
Width
5.2?mm?/ 0.205?inches
Height
69.7?mm?/ 2.744?inches
Height from upper-edge of DIN-rail
51.7?mm?/ 2.035?inch
Depth from upper-edge of DIN-rail
51.7?mm?/ 2.035?inches
Depth
69.7?mm?/ 2.744?inch
Potential Marking
N/L
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
orange
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.204MJ
Weight
10g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
22 (TOPJOB S)
ETIM 9.0
EC000897
ETIM 8.0
EC000897
ECCN
NO US CLASSIFICATION
PU (SPU)
50?pcs
Packaging type
box
Country of origin
DE
GTIN
4055143550918
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
ATEX: PTB 03 ATEX 1162 U / IECEx: PTB 03.0004U (Ex eb IIC Gb)
Rated voltage (III / 3)
500V
Rated impulse voltage (III / 3)
6kV
Rated current
24A
Current at conductor cross-section (max.) mm2
28A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
300V
Rated current UL (Use Group B)
20A
Rated voltage UL (Use Group C)
300V
Rated current UL (Use Group C)
20A
Rated voltage UL (Use Group D)
600V
Rated current UL (Use Group D)
5A
Rated voltage CSA (Use Group B)
300V
Rated current CSA (Use Group B)
20A
Rated voltage CSA (Use Group C)
300V
Rated current CSA (Use Group C)
20A
Reference hazardous areas
See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Rated voltage EN (Ex e II)
440V
Rated current (Ex e II)
20A
Rated current (Ex e II) with jumper
18A
Power loss, per pole (potential)
0.766W
Rated current I<sub>N</sub> for specified power loss
24A
Resistance value for specified, current-dependent power loss
0.001Ω
Connection technology
Push-in CAGE CLAMP?
Total number of connection points
2
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm2
Solid conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Solid conductor; push-in termination
0.75 … 4?mm2?/ 18 … 12?AWG
Fine-stranded conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Fine-stranded conductor; with insulated ferrule
1 … 2.5?mm2?/ 18 … 14?AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5?mm2?/ 18 … 14?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12?mm?/ 0.39 … 0.47?inches
Wiring direction
Front-entry wiring
Number of connection points 2
2

Specifications may be subject to change without notice