Product Model
2002-3211/1000-411

Selling Points
- 1Triple-deck design for increased connectivity.
- 2Equipped with a 1N4007 diode for enhanced protection.
- 3Compatible with DIN-rail 35 x 15 and 35 x 7.5.
- 4Push-in CAGE CLAMP connections for easy wiring.
- 5Rated for 0.5 A current and 600 V voltage.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 6 | Total number of potentials | 3 |
Number of levels | 3 | Width | 5.2?mm?/ 0.205?inches |
Height | 93.3?mm?/ 3.673?inches | Depth from upper-edge of DIN-rail | 69.5?mm?/ 2.736?inches |
Mounting type | DIN-35 rail | Marking level | Center/side marking |
Note (material data) | Information on material specifications can be found here | Color | gray |
Material group | I | Insulation material (main housing) | Polyamide (PA66) |
Flammability class per UL94 | V0 | Fire load | 0.364MJ |
Weight | 17.6g | Processing temperature | -35 … +85?°C |
Continuous operating temperature | -60 … +105?°C | Product Group | 22 (TOPJOB S) |
eCl@ss 10.0 | 27-14-11-27 | eCl@ss 9.0 | 27-14-11-27 |
ETIM 9.0 | EC000903 | ETIM 8.0 | EC000903 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 50?pcs |
Packaging type | box | Country of origin | DE |
GTIN | 4045454375690 | Customs tariff number | 8536904000 |
CAS-No. | 7439-92-1 | REACH Candidate List Substance | 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol |
RoHS Compliance Status | Compliant,With Exemption | RoHS Exemption | 7(a) |
SCIP notification number (Austria) | 59ef1f94-10bd-46f1-b604-15ca1e115d59 | SCIP notification number (Belgium) | 2465f38f-60d6-400d-a326-0e475a8c1bed |
SCIP notification number (Bulgaria) | dbb760cf-bf87-4c45-8052-988ed4a2829a | SCIP notification number (Czech Republic) | d755b2bb-30c2-4cf0-9363-094ea314b8d2 |
SCIP notification number (Denmark) | e0e03f70-1998-418e-9ee1-2d25365c0454 | SCIP notification number (Finland) | 374f1f97-de1d-406a-93cc-f93fa18df07e |
SCIP notification number (France) | 25d700f5-1722-40c5-88cf-5cd10b9a4125 | SCIP notification number (Germany) | c7a644a3-02f1-48f8-bdf9-62653058d4c1 |
SCIP notification number (Hungary) | bdcbd633-1dea-426e-a235-4042e4c2b5de | SCIP notification number (Italy) | a205f41a-6fb8-4325-a5ab-b0386d08266d |
SCIP notification number (Netherlands) | a240c361-caa5-4d2c-8567-c700db74e708 | SCIP notification number (Poland) | ca86283c-76af-4a52-82e5-4851dc0f074a |
SCIP notification number (Romania) | 020dd723-0da1-4eb4-9576-e005d575635a | SCIP notification number (Sweden) | cd80a751-3855-4720-bd20-d11ed6218e27 |
Ratings per | IEC/EN 60947-7-1 | Rated current | 0.5A |
Approvals per | UL 1059 | Nominal voltage | 250V |
Reverse voltage | 1,000V | Connection technology | Push-in CAGE CLAMP? |
Actuation type | Operating tool | Connectable conductor materials | Copper |
Nominal cross-section | 2.5 mm2 | Solid conductor | 0.25 … 4?mm2?/ 22 … 12?AWG |
Solid conductor; push-in termination | 0.75 … 4?mm2?/ 18 … 12?AWG | Fine-stranded conductor | 0.25 … 4?mm2?/ 22 … 12?AWG |
Fine-stranded conductor; with insulated ferrule | 0.25 … 2.5?mm2?/ 22 … 14?AWG | Fine-stranded conductor; with ferrule; push-in termination | 1 … 2.5?mm2?/ 18 … 14?AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. | Strip length | 10 … 12?mm?/ 0.39 … 0.47?inches |
Wiring direction | Front-entry wiring | Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 | Spectrum/Installation location | Service life test, Category?1, Class?A/B |
Function test with noise-like vibration | Test passed according to Section 8 of the standard | Frequency | f1= 5 Hz to f2= 150 Hz |
Acceleration | 5g (highest test level used for all axes) | Test duration per axis | 5 h |
Test directions | X, Y and Z axes | Monitoring for contact faults/interruptions | Passed |
Voltage drop measurement before and after each axis | Passed | Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
Extended test scope: Monitoring for contact faults/interruptions | Passed | Extended test scope: Voltage drop measurement before and after each axis | Passed |
Shock test | Test passed according to Section 10 of the standard | Shock form | Half sine |
Shock duration | 30 ms | Number of shocks per axis | 3 pos. und 3 neg. |
Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice