wago 2002-3217

Selling Points

  • 1High Current Rating: Supports up to 24A of current.
  • 2Versatile Wiring: Accommodates wires from 0.25mm² to 4mm² or #22AWG to #12AWG.
  • 3Durable Construction: Made from high-quality polyamide 6.6 material.
  • 4Easy Installation: Uses push-in CAGE CLAMP connections for quick and secure mounting.
  • 5Compliant with Regulations: Meets Ex e II and UL standards for safety and reliability.
Product Details
2002-3217
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
6
Total number of potentials
3
Number of levels
3
Number of jumper slots
6
Width
5.2?mm?/ 0.205?inches
Height
93.3?mm?/ 3.673?inches
Depth from upper-edge of DIN-rail
69.5?mm?/ 2.736?inches
Potential Marking
PE/N/L
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.334MJ
Weight
19.7g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-41
eCl@ss 9.0
27-14-11-41
ETIM 9.0
EC000901
ETIM 8.0
EC000901
ECCN
NO US CLASSIFICATION
PU (SPU)
50?pcs
Packaging type
box
Country of origin
DE
GTIN
4044918691208
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
ATEX: PTB 03 ATEX 1162 U / IECEx: PTB 03.0004U (Ex eb IIC Gb)
Rated voltage (III / 3)
500V
Rated impulse voltage (III / 3)
6kV
Rated current
24A
Current at conductor cross-section (max.) mm2
28A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
300V
Rated current UL (Use Group B)
20A
Rated voltage UL (Use Group C)
300V
Rated current UL (Use Group C)
20A
Rated voltage UL (Use Group D)
600V
Rated current UL (Use Group D)
5A
Rated voltage CSA (Use Group B)
300V
Rated current CSA (Use Group B)
20A
Rated voltage CSA (Use Group C)
300V
Rated current CSA (Use Group C)
20A
Reference hazardous areas
See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Rated voltage EN (Ex e II)
440V
Rated current (Ex e II)
19A
Rated current (Ex e II) with jumper
17A
Power loss, per pole (potential)
0.96W
Rated current I<sub>N</sub> for specified power loss
24A
Resistance value for specified, current-dependent power loss
0.001Ω
Connection technology
Push-in CAGE CLAMP?
Total number of connection points
3
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm2
Solid conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Solid conductor; push-in termination
0.75 … 4?mm2?/ 18 … 12?AWG
Fine-stranded conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5?mm2?/ 22 … 14?AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5?mm2?/ 18 … 14?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12?mm?/ 0.39 … 0.47?inches
Wiring direction
Front-entry wiring
Number of connection points 2
3
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice