Product Model
2002-553

Selling Points
- 1High-Performance Design: Ideal for jumper contact slots with a 3-pole configuration.
- 2Durable Construction: Gray housing made of polyamide (PA66) for insulation.
- 3Easy Connection: Push-in CAGE CLAMP connection technology for fast and vibration-proof connections.
- 4Safety Features: Secure female plugs via locking levers and strain relief plates to prevent mis-mating.
- 5Versatile Application: Suitable for various industrial applications with a rated current of 24 A and voltage of 500 V.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Safety information | According to EN 61984, pluggable connectors without current interrupting capacity must not be mated or unmated when live or under load. | Clamping units | 3 |
Total number of potentials | 3 | Width | 15.6?mm?/ 0.614?inches |
Module width | 5.2?mm?/ 0.205?inches | Marking level | Center/side marking |
Note (material data) | Information on material specifications can be found here | Color | gray |
Insulation material (main housing) | Polyamide (PA66) | Flammability class per UL94 | V0 |
Fire load | 0.213MJ | Weight | 8.2g |
Product Group | 22 (TOPJOB S) | eCl@ss 10.0 | 27-14-11-51 |
eCl@ss 9.0 | 27-14-11-51 | ETIM 9.0 | EC002021 |
ETIM 8.0 | EC002021 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 25?pcs | Packaging type | box |
Country of origin | DE | GTIN | 4045454178345 |
Customs tariff number | 8536904000 | RoHS Compliance Status | Compliant,No Exemption |
Rated voltage (III / 3) | 500V | Rated impulse voltage (III / 3) | 6kV |
Rated current | 24A | Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 |
Connection technology | Push-in CAGE CLAMP? | Actuation type | Operating tool |
Nominal cross-section | 2.5 mm2 | Solid conductor | 0.25 … 4?mm2?/ 22 … 12?AWG |
Solid conductor; push-in termination | 0.75 … 4?mm2?/ 18 … 12?AWG | Fine-stranded conductor | 0.25 … 4?mm2?/ 22 … 12?AWG |
Fine-stranded conductor; with insulated ferrule | 0.25 … 2.5?mm2?/ 22 … 14?AWG | Fine-stranded conductor; with ferrule; push-in termination | 1 … 2.5?mm2?/ 18 … 14?AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. | Strip length | 10 … 12?mm?/ 0.39 … 0.47?inches |
Number of poles | 3 | Wiring direction | Side-entry wiring |
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 | Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
Spectrum/Installation location | Service life test, Category?1, Class?A/B | Function test with noise-like vibration | Test passed according to Section 8 of the standard |
Frequency | f1= 5 Hz to f2= 150 Hz | Acceleration | 5g (highest test level used for all axes) |
Test duration per axis | 5 h | Test directions | X, Y and Z axes |
Monitoring for contact faults/interruptions | Passed | Voltage drop measurement before and after each axis | Passed |
Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard | Extended test scope: Monitoring for contact faults/interruptions | Passed |
Extended test scope: Voltage drop measurement before and after each axis | Passed | Shock test | Test passed according to Section 10 of the standard |
Shock form | Half sine | Shock duration | 30 ms |
Number of shocks per axis | 3 pos. und 3 neg. | Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice