wago 2003-6662

Selling Points

  • 1Multilevel installation terminal block with operating slots.
  • 2Accommodates two feed-through poles and a protective earth (2P+PE).
  • 3Supports wire sizes ranging from 0.25mm² to 4mm² (#22AWG to #12AWG).
  • 4Rated for currents of 20A and 25A with Push-in CAGE CLAMP spring connections.
  • 5Designed for DIN-35 rail mounting with a width of 5.2mm.
Product Details
2003-6662
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
5
Total number of potentials
3
Number of levels
3
Width
5.2?mm?/ 0.205?inches
Height
110?mm?/ 4.331?inches
Depth from upper-edge of DIN-rail
45.2?mm?/ 1.78?inches
Potential Marking
L/L/PE
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.309MJ
Weight
19.9g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
ETIM 9.0
EC001329
ETIM 8.0
EC001329
ECCN
NO US CLASSIFICATION
PU (SPU)
50?pcs
Packaging type
box
Country of origin
CN
GTIN
4055143987219
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings
Potential - potential
Ratings per
IEC/EN 60947-7-1
Rated voltage (III / 3)
250V
Rated impulse voltage (III / 3)
4kV
Rated current
20A
Current at conductor cross-section (max.) mm2
25A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Rated current (note)
Maximum current depends on accessories used.
Ratings per 2
IEC/EN 60947-7-1
Rated voltage (III/3) 2
400V
Rated surge voltage (III/3) 2
6kV
Rated current 2
20A
Current at conductor cross-section (max.) 2
25A
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
250V
Rated current UL (Use Group B)
6.3A
Rated voltage UL (Use Group C)
150V
Rated current UL (Use Group C)
6.3A
Rated voltage UL (Use Group D)
250V
Rated current UL (Use Group D)
6.3A
Rated voltage CSA (Use Group B)
300V
Rated current CSA (Use Group B)
20A
Rated voltage CSA (Use Group D)
300V
Rated current CSA (Use Group D)
10A
Power loss, per pole (potential)
0.133W
Rated current I<sub>N</sub> for specified power loss
10A
Resistance value for specified, current-dependent power loss
0.001Ω
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm2
Solid conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Solid conductor; push-in termination
0.75 … 4?mm2?/ 18 … 12?AWG
Fine-stranded conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5?mm2?/ 22 … 14?AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5?mm2?/ 18 … 14?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12?mm?/ 0.39 … 0.47?inches
Wiring direction
Front-entry wiring

Specifications may be subject to change without notice