Product Model
2004-404

Selling Points
- 1Insulated Push-In Design: Easy to use with rail-mounted terminal blocks.
- 2High Electrical Rating: Supports up to 800 VAC and 32 A.
- 3Compact Dimensions: 0.748 in H x 0.898 in W x 0.161 in D.
- 4Light Gray Housing: Durable and visually appealing.
- 5Ex-Approved for Safety: Meets international safety standards for industrial use.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Width | 22.8?mm?/ 0.898?inches | Height | 4.1?mm?/ 0.161?inches |
Depth | 19?mm?/ 0.748?inches | Jumper assignment | 1-2-3-4 |
Note (material data) | Information on material specifications can be found here | Color | light gray |
Material group | I | Insulation material (main housing) | Polyamide (PA66) |
Flammability class per UL94 | V0 | Fire load | 0.015MJ |
Weight | 3.1g | Processing temperature | -35 … +85?°C |
Continuous operating temperature | -60 … +105?°C | Product Group | 22 (TOPJOB S) |
eCl@ss 10.0 | 27-14-11-40 | eCl@ss 9.0 | 27-14-11-40 |
ETIM 9.0 | EC000489 | ETIM 8.0 | EC000489 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 25?pcs |
Packaging type | bag | Country of origin | DE |
GTIN | 4055143699846 | Customs tariff number | 8536698000 |
RoHS Compliance Status | Compliant,No Exemption | Rated voltage (III / 3) | 800V |
Rated current | 32A | Rated current (Ex e II) | 30A |
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 | Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
Spectrum/Installation location | Service life test, Category?1, Class?A/B | Function test with noise-like vibration | Test passed according to Section 8 of the standard |
Frequency | f1= 5 Hz to f2= 150 Hz | Acceleration | 5g (highest test level used for all axes) |
Test duration per axis | 5 h | Test directions | X, Y and Z axes |
Monitoring for contact faults/interruptions | Passed | Voltage drop measurement before and after each axis | Passed |
Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard | Extended test scope: Monitoring for contact faults/interruptions | Passed |
Extended test scope: Voltage drop measurement before and after each axis | Passed | Shock test | Test passed according to Section 10 of the standard |
Shock form | Half sine | Shock duration | 30 ms |
Number of shocks per axis | 3 pos. und 3 neg. | Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice