wago 2004-436

Selling Points

  • 1The WAGO 2004-436 features insulated jumper bars to ensure safe and reliable connections.
  • 2Suitable for cross-connection applications, this jumper bar can connect 1 to 6 terminals.
  • 3Designed to handle nominal currents up to 32 A, making it suitable for demanding electrical systems.
  • 4Built with high-quality materials for long-lasting performance and resistance to environmental factors.
  • 5Push-in type terminals simplify the installation process, reducing setup time and effort.
Product Details
2004-436
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
35.2?mm?/ 1.386?inches
Height
4.1?mm?/ 0.161?inches
Depth
19?mm?/ 0.748?inches
Jumper assignment
1-6
Design
spanning
Note (material data)
Information on material specifications can be found here
Color
light gray
Fire load
0.017MJ
Weight
2.8g
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-40
eCl@ss 9.0
27-14-11-40
ETIM 9.0
EC000489
ETIM 8.0
EC000489
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
bag
Country of origin
DE
GTIN
4044918583107
Customs tariff number
8536698000
RoHS Compliance Status
Compliant,No Exemption
Rated voltage (III / 3)
800V
Rated current
32A
Rated current (Ex e II)
30A
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed