Product Model
2006-1208

Selling Points
- 1Push-in CAGE CLAMP Technology: Easy and secure wire connection.
- 2Ex e II Applications: Suitable for hazardous environments.
- 3DIN-Rail Mounting: Versatile and space-efficient rail mounting.
- 4Front-Entry Wiring: Convenient and accessible wiring direction.
- 5Polyamide Insulation: High-quality, durable insulation material.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 2 | Total number of potentials | 1 |
Number of levels | 1 | Number of jumper slots | 2 |
Width | 7.5?mm?/ 0.295?inches | Height | 57.5?mm?/ 2.26?inches |
Depth from upper-edge of DIN-rail | 32.9?mm?/ 1.295?inches | Mounting type | DIN-35 rail |
Marking level | Center/side marking | Note (material data) | Information on material specifications can be found here |
Color | white | Material group | I |
Insulation material (main housing) | Polyamide (PA66) | Flammability class per UL94 | V0 |
Fire load | 0.178MJ | Weight | 17.3g |
Processing temperature | -35 … +85?°C | Continuous operating temperature | -60 … +105?°C |
Product Group | 22 (TOPJOB S) | eCl@ss 10.0 | 27-14-11-41 |
eCl@ss 9.0 | 27-14-11-41 | ETIM 9.0 | EC000901 |
ETIM 8.0 | EC000901 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 50?pcs | Packaging type | box |
Country of origin | DE | GTIN | 4050821189121 |
Customs tariff number | 8536904000 | RoHS Compliance Status | Compliant,No Exemption |
Ratings per | IEC/EN 60947-7-2 | Connection technology | Push-in CAGE CLAMP? |
Actuation type | Operating tool | Connectable conductor materials | Copper |
Nominal cross-section | 6 mm2 | Solid conductor | 0.5 … 10?mm2?/ 20 … 8?AWG |
Solid conductor; push-in termination | 2.5 … 10?mm2?/ 14 … 8?AWG | Fine-stranded conductor | 0.5 … 10?mm2?/ 20 … 8?AWG |
Fine-stranded conductor; with insulated ferrule | 0.5 … 6?mm2?/ 20 … 10?AWG | Fine-stranded conductor; with ferrule; push-in termination | 2.5 … 6?mm2?/ 16 … 10?AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. | Strip length | 13 … 15?mm?/ 0.51 … 0.59?inches |
Wiring direction | Front-entry wiring | Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 | Spectrum/Installation location | Service life test, Category?1, Class?A/B |
Function test with noise-like vibration | Test passed according to Section 8 of the standard | Frequency | f1= 5 Hz to f2= 150 Hz |
Acceleration | 5g (highest test level used for all axes) | Test duration per axis | 5 h |
Test directions | X, Y and Z axes | Monitoring for contact faults/interruptions | Passed |
Voltage drop measurement before and after each axis | Passed | Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
Extended test scope: Monitoring for contact faults/interruptions | Passed | Extended test scope: Voltage drop measurement before and after each axis | Passed |
Shock test | Test passed according to Section 10 of the standard | Shock form | Half sine |
Shock duration | 30 ms | Number of shocks per axis | 3 pos. und 3 neg. |
Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice