wago 2006-1401

Selling Points

  • 1High Amperage Rating: Supports up to 32A for reliable power distribution.
  • 2Durable Construction: Made from polyamide 6.6 insulation for long-lasting performance.
  • 3Efficient Wiring: Push-in CAGE CLAMP connection technology simplifies wiring.
  • 4Versatile Mounting: Compatible with DIN Rail 35 x 15 and 35 x 7.5 for flexible installation.
  • 5Enhanced Safety: Meets UL 1059 and IEC/EN 60947-7-1 standards for safety compliance.
Product Details
2006-1401
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
4
Total number of potentials
1
Number of levels
1
Number of jumper slots
2
Width
7.5 mm / 0.295 inches
Height
89.3 mm / 3.516 inches
Depth from upper-edge of DIN-rail
32.9 mm / 1.295 inches
Depth
39.5 mm / 1.555 inches
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.284MJ
Weight
16.3g
Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C
ECCN
NO US CLASSIFICATION
PU (SPU)
25 pcs
Packaging type
Box
Country of origin
DE
GTIN
4066966595772
Customs tariff number
85369010000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
ATEX: PTB 05 ATEX 1030 U / IECEx: PTB 05.0014U (Ex eb IIC Gb)
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated current
41A
Current at conductor cross-section (max.) mm2
53A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
50A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
50A
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
50A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
50A
Reference hazardous areas
See application instructions in section “Knowledge andDownloads – Documentation – Additional Information: Technical Section; Technical Explications”
Rated voltage EN (Ex e II)
550V
Rated current (Ex e II)
36A
Rated current (Ex e II) with jumper
33A
Rated current I<sub>N</sub> for specified power loss
41A
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
6 mm2
Solid conductor
0.5 … 10 mm2 / 20 … 8 AWG
Solid conductor; push-in termination
2.5 … 10 mm2 / 14 … 8 AWG
Stranded conductor
0.5 … 10 mm2 / 20 … 8 AWG
Fine-stranded conductor
0.5 … 10 mm2 / 20 … 8 AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 6 mm2 / 20 … 10 AWG
Fine-stranded conductor; with ferrule; push-in termination
2.5 … 6 mm2 / 16 … 10 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
13 … 15 mm / 0.51 … 0.59 inches
Wiring direction
Front-entry wiring

Specifications may be subject to change without notice