wago 2006-1621

Selling Points

  • 1Securely holds 5 x 30 mm miniature metric fuses.
  • 2Easily detect blown fuses with the integrated LED indicator.
  • 3Simplifies connection with a secure push-in mechanism.
  • 4Designed for DIN-rail 35 x 15 and 35 x 7.5 mounting.
  • 5Operates within 12 - 30 V, suitable for various applications.
Product Details
2006-1621
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
2
Total number of potentials
1
Number of levels
1
Number of jumper slots
2
Width
7.5?mm?/ 0.295?inches
Height
96.3?mm?/ 3.791?inches
Depth from upper-edge of DIN-rail
59?mm?/ 2.323?inches
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.455MJ
Weight
24.7g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-16
eCl@ss 9.0
27-14-11-16
ETIM 9.0
EC000899
ETIM 8.0
EC000899
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
box
Country of origin
CN
GTIN
4045454821173
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60947-7-3
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated current
10A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Ratings (note)
Electrical ratings are given by the fuse.
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
15A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
15A
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
15A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
15A
Power loss (max.) P<sub>l (max.)</sub> (note)
When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN?60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
Power loss P<sub>l</sub> max. overload and short-circuit protection (individual arrangement)
1.6W
Power loss P<sub>l</sub> max. overload and short-circuit protection (group arrangement)
1.6W
Power loss P<sub>l</sub> max. short-circuit protection (individual arrangement)
2.5W
Power loss P<sub>l</sub> max. short-circuit protection (group arrangement)
2.5W
Fuse receptacle
pivoting
Fuse type
Cylindrical fuse; 5 x 30 mm
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
6 mm2
Solid conductor
0.5 … 10?mm2?/ 20 … 8?AWG
Solid conductor; push-in termination
1 … 10?mm2?/ 14 … 8?AWG
Fine-stranded conductor
0.5 … 10?mm2?/ 20 … 8?AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 6?mm2?/ 20 … 10?AWG
Fine-stranded conductor; with ferrule; push-in termination
2.5 … 6?mm2?/ 16 … 10?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
13 … 15?mm?/ 0.51 … 0.59?inches
Wiring direction
Front-entry wiring
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice