wago 2006-1621/1000-542

Selling Points

  • 1Pivoting Fuse Holder for Easy Access
  • 2Supports 5 x 30 mm Miniature Metric Fuses
  • 3LED Blown Fuse Indication for Safety
  • 4DIN-Rail Mounting for Compact Installation
  • 5Push-in CAGE CLAMP Connections for Secure Wiring
Product Details
2006-1621/1000-542
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
2
Total number of potentials
1
Number of levels
1
Number of jumper slots
2
Width
7.5?mm?/ 0.295?inches
Height
96.3?mm?/ 3.791?inches
Depth from upper-edge of DIN-rail
59?mm?/ 2.323?inches
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.443MJ
Weight
25.1g
Processing temperature
-35 … +50 °C
Continuous operating temperature
-60 … +50 °C
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-16
eCl@ss 9.0
27-14-11-16
ETIM 9.0
EC000899
ETIM 8.0
EC000899
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
box
Country of origin
DE
GTIN
4045454824006
Customs tariff number
8536904000
CAS-No.
1303-86-2
REACH Candidate List Substance
Diboron trioxide
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
7(a)
SCIP notification number (Austria)
f5bed8bb-2123-4645-a164-180fa0d4d651
SCIP notification number (Belgium)
ddfa03bf-871b-4aab-9454-7ffd775dfd65
SCIP notification number (Bulgaria)
313e9bf9-d70e-496f-be58-be9ff75c03ea
SCIP notification number (Czech Republic)
4cae27f8-86b0-4705-bd0f-7c2508fa5bba
SCIP notification number (Denmark)
2440d3d7-eb82-4d3b-ab82-9e4cd0a9c7bb
SCIP notification number (Finland)
0698c67f-a888-423c-8b82-7e4ac7be45dd
SCIP notification number (France)
05f8726d-c070-4d51-94d5-6fa673b889f6
SCIP notification number (Germany)
31a31a54-4d2d-4bf3-9e78-64f7ee6c4e1e
SCIP notification number (Hungary)
a56a7c98-871e-407d-95ba-8101fa1ea1d1
SCIP notification number (Italy)
c53487fa-dd4f-4f04-ac84-b63ac19f27c1
SCIP notification number (Netherlands)
a7276a3b-a386-4e42-9dbd-e7e4b8bdfed1
SCIP notification number (Poland)
66faac6e-bc6e-4c74-a2f0-43ff6f29d4f5
SCIP notification number (Romania)
f1fa5cfc-ca35-418a-9c27-ccd729646cf7
SCIP notification number (Sweden)
b9b97f48-fcab-4d3b-87c8-5e74a5ee2516
Ratings per
IEC/EN 60947-7-3
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated current
10A
Blown fuse indication
30 … 65 V
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Ratings (note)
Electrical ratings are given by the fuse and blown fuse indication.
Rated current (note)
Leakage current in case of a blown fuse: LED 2.2 mA (at 48 V operating voltage)
Ratings per 2
IEC/EN 60947-7-3
Rated voltage (III/3) 2
65V
Rated surge voltage (III/3) 2
1.5kV
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
65V
Rated current UL (Use Group B)
15A
Rated voltage UL (Use Group C)
65V
Rated current UL (Use Group C)
15A
Rated voltage CSA (Use Group B)
65V
Rated current CSA (Use Group B)
15A
Rated voltage CSA (Use Group C)
65V
Rated current CSA (Use Group C)
15A
Power loss (max.) P<sub>l (max.)</sub> (note)
When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN?60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
Power loss P<sub>l</sub> max. overload and short-circuit protection (individual arrangement)
1.6W
Power loss P<sub>l</sub> max. overload and short-circuit protection (group arrangement)
1.6W
Power loss P<sub>l</sub> max. short-circuit protection (individual arrangement)
2.5W
Power loss P<sub>l</sub> max. short-circuit protection (group arrangement)
2.5W
Fuse receptacle
pivoting
Fuse type
Cylindrical fuse; 5 x 30 mm
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
6 mm2
Solid conductor
0.5 … 10?mm2?/ 20 … 8?AWG
Solid conductor; push-in termination
1 … 10?mm2?/ 14 … 8?AWG
Fine-stranded conductor
0.5 … 10?mm2?/ 20 … 8?AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 6?mm2?/ 20 … 10?AWG
Fine-stranded conductor; with ferrule; push-in termination
2.5 … 6?mm2?/ 16 … 10?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
13 … 15?mm?/ 0.51 … 0.59?inches
Wiring direction
Front-entry wiring
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice