Product Model

2006-931/1000-859

In Stock
Last updated: 2025/4/19
wago 2006-931/1000-859

Selling Points

  • 17.4 mm wide, perfect for space-constrained applications.
  • 2Operates with a supply voltage of 380-500Vdc.
  • 3Visual confirmation of fuse status with an integrated LED light.
  • 4Easy to remove and replace fuses with a simple pull-tab mechanism.
  • 5Gray color, designed for plug-in mounting, ensuring secure installation.
Product Details
2006-931/1000-859
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Width
7.4?mm?/ 0.291?inches
Marking level
Center marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.106MJ
Weight
7.2g
Continuous operating temperature
-60 … +105?°C
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-49
eCl@ss 9.0
27-14-11-49
ETIM 9.0
EC002018
ETIM 8.0
EC002018
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
box
Country of origin
DE
GTIN
4045454821098
Customs tariff number
8536694040
CAS-No.
1317-36-8
REACH Candidate List Substance
2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
7(a)
SCIP notification number (Austria)
1e228d52-8cac-4076-984f-5e47d3b13706
SCIP notification number (Belgium)
f90e577e-48e1-4b4e-b1de-8b47417d6ca2
SCIP notification number (Bulgaria)
caad2d82-8129-4146-8917-c5b59d9cce50
SCIP notification number (Czech Republic)
e6826d3a-e7d6-454f-8033-6ee4500dbe86
SCIP notification number (Denmark)
e5f98190-d02f-46c9-acf1-c48258fb9b06
SCIP notification number (Finland)
4548aec2-40b2-4264-92cc-651a9ad88dbd
SCIP notification number (France)
b5256235-219d-409c-a144-ce1457d57e8b
SCIP notification number (Germany)
1a1f3794-fa8e-4c01-857e-046ba603f0b0
SCIP notification number (Hungary)
2b8a33d0-8aa9-42fb-9f68-1881a8938f32
SCIP notification number (Italy)
356bc2bf-aba1-44e5-90b8-a8c2ffd487f6
SCIP notification number (Netherlands)
f609c9e8-0348-4b8f-bf7b-e9dd42aae4ad
SCIP notification number (Poland)
2776c869-cb48-4386-b7fd-42f69141ae68
SCIP notification number (Romania)
76318ecc-16c5-4eee-9ccd-8b65a07b743b
SCIP notification number (Sweden)
09062e21-1d93-4ec0-ac88-16d6575eff43
Rated voltage (III / 3)
800V
Rated current
10A
Operation status indicator
380 … 500?V
Blown fuse indication
with indicator lamp
Ratings (note)
Electrical ratings are given by the fuse and blown fuse indication.
Rated current (note)
Leakage current in case of a blown fuse: LED 2 mA
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
500V
Rated current UL (Use Group B)
15A
Rated voltage UL (Use Group C)
500V
Rated current UL (Use Group C)
15A
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
15A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
15A
Power loss (max.) P<sub>l (max.)</sub> (note)
When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN?60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
Fuse type
Cylindrical fuse; ?" x 1?"
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice