Product Model
2007-8874

Selling Points
- 1Compact 1-deck/level design with side/lateral and center marking slots.
- 2Suitable for current transformer (CT) and voltage transformer (VT) connections.
- 3Supports wire sizes from 0.5mm² to 10mm² or #20AWG to #8AWG.
- 4Utilizes Push-in CAGE CLAMP spring connections for easy installation.
- 5Compliant with RoHS standards and V-0 flammability rating.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Number of levels | 1 | Width | 127?mm?/ 5?inches |
Height | 99.6?mm?/ 3.921?inches | Depth from upper-edge of DIN-rail | 65.3?mm?/ 2.571?inches |
Module width | 8?mm?/ 0.315?inches | Mounting type | DIN-35 rail |
Marking level | Center/side marking | Note (material data) | Information on material specifications can be found here |
Color | multi-colored | Material group | I |
Insulation material (main housing) | Polyamide (PA66) | Flammability class per UL94 | V0 |
Fire load | 6.477MJ | Weight | 402.4g |
Processing temperature | -35 … +85?°C | Continuous operating temperature | -60 … +105?°C |
Product Group | 22 (TOPJOB S) | eCl@ss 10.0 | 27-14-11-47 |
eCl@ss 9.0 | 27-14-11-47 | ETIM 9.0 | EC000276 |
ETIM 8.0 | EC000276 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 1?pcs | Packaging type | box |
Country of origin | DE | GTIN | 4055143070294 |
Customs tariff number | 8536904000 | CAS-No. | 7439-92-1 |
REACH Candidate List Substance | Lead | RoHS Compliance Status | Compliant,With Exemption |
RoHS Exemption | 6(c) | SCIP notification number (Austria) | be090492-316a-4da2-8615-f61e4d86728a |
SCIP notification number (Belgium) | 445f69c5-a5ef-4db5-ba0d-67db0ff386aa | SCIP notification number (Bulgaria) | 2cf95ddd-9e24-4057-8a95-0872de205fd5 |
SCIP notification number (Czech Republic) | dd82830c-1bc6-4249-be16-2a84f8eae2f3 | SCIP notification number (Denmark) | fb14f858-96a6-4850-b673-5cfed08e7f46 |
SCIP notification number (Finland) | 784d71b6-1ff6-496f-84a9-ec5e6405fb71 | SCIP notification number (France) | 46ebaf43-c978-422a-9b07-7ac1d06b43c1 |
SCIP notification number (Germany) | d14407af-157c-4e3b-9d7e-8c4ac153311a | SCIP notification number (Hungary) | e6882aae-9fa8-4576-aaac-44abb965d1a5 |
SCIP notification number (Italy) | dd3c6457-22e6-437d-8d9f-0f7c0a4a3360 | SCIP notification number (Netherlands) | 2b7a5329-22ed-44c3-bd9b-a39ac1ea3dd3 |
SCIP notification number (Poland) | 98a2045c-d4ac-4d19-8465-e3593ecf3353 | SCIP notification number (Romania) | 52920352-634b-45e1-95e6-c249bdfae9ae |
SCIP notification number (Sweden) | 80f65056-a8cb-4be4-945f-953fba3801a1 | Rated voltage (III / 3) | 500V |
Rated impulse voltage (III / 3) | 6kV | Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 |
Connection technology | Push-in CAGE CLAMP? | Actuation type | Operating tool |
Connectable conductor materials | Copper | Nominal cross-section | 6 mm2 / 10 AWG |
Solid conductor | 0.5 … 10?mm2?/ 20 … 8?AWG | Solid conductor; push-in termination | 1 … 10?mm2?/ 14 … 8?AWG |
Fine-stranded conductor | 0.5 … 10?mm2?/ 20 … 8?AWG | Fine-stranded conductor; with insulated ferrule | 0.5 … 6?mm2?/ 20 … 10?AWG |
Fine-stranded conductor; with uninsulated ferrule | 1.5 … 6?mm2?/ 16 … 10?AWG | Fine-stranded conductor; with ferrule; push-in termination | 2.5 … 6?mm2?/ 16 … 10?AWG |
Strip length | 13 … 15?mm?/ 0.51 … 0.59?inches | Wiring direction | Front-entry wiring |
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 | Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
Spectrum/Installation location | Service life test, Category?1, Class?A/B | Function test with noise-like vibration | Test passed according to Section 8 of the standard |
Frequency | f1= 5 Hz to f2= 150 Hz | Acceleration | 5g (highest test level used for all axes) |
Test duration per axis | 5 h | Test directions | X, Y and Z axes |
Monitoring for contact faults/interruptions | Passed | Voltage drop measurement before and after each axis | Passed |
Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard | Extended test scope: Monitoring for contact faults/interruptions | Passed |
Extended test scope: Voltage drop measurement before and after each axis | Passed | Shock test | Test passed according to Section 10 of the standard |
Shock form | Half sine | Shock duration | 30 ms |
Number of shocks per axis | 3 pos. und 3 neg. | Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice