Product Model
2010-1309

Selling Points
- 1Ensures high reliability in hazardous environments.
- 2Easy and secure wire connection.
- 3Versatile and space-efficient design.
- 4Enhanced readability for precise connections.
- 5Handles high current requirements efficiently.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 3 | Total number of potentials | 1 |
Number of levels | 1 | Number of jumper slots | 2 |
Width | 10?mm?/ 0.394?inches | Height | 89?mm?/ 3.504?inches |
Depth from upper-edge of DIN-rail | 36.9?mm?/ 1.453?inches | Depth | 43.5 mm / 1.713 inches |
Mounting type | DIN-35 rail | Marking level | Center/side marking |
Note (material data) | Information on material specifications can be found here | Color | light gray |
Material group | I | Insulation material (main housing) | Polyamide (PA66) |
Flammability class per UL94 | V0 | Fire load | 0.391MJ |
Weight | 23.3g | Processing temperature | -35 … +85?°C |
Continuous operating temperature | -60 … +105?°C | eCl@ss 10.0 | 27-14-11-20 |
eCl@ss 9.0 | 27-14-11-20 | ETIM 9.0 | EC000897 |
ETIM 8.0 | EC000897 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 25?pcs | Packaging type | box |
Country of origin | DE | GTIN | 4055143645393 |
Customs tariff number | 85369010000 | RoHS Compliance Status | Compliant,No Exemption |
Ratings per | ATEX: PTB 05 ATEX 1070 U / IECEx: PTB 06.0003U (Ex eb IIC Gb) | Rated voltage (III / 3) | 800V |
Rated impulse voltage (III / 3) | 8kV | Rated current | 57A |
Current at conductor cross-section (max.) mm2 | 76A | Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 |
Approvals per | CSA 22.2 No 158 | Rated voltage UL (Use Group B) | 600V |
Rated current UL (Use Group B) | 65A | Rated voltage UL (Use Group C) | 600V |
Rated current UL (Use Group C) | 65A | Rated voltage CSA (Use Group B) | 600V |
Rated current CSA (Use Group B) | 65A | Rated voltage CSA (Use Group C) | 600V |
Rated current CSA (Use Group C) | 65A | Reference hazardous areas | See application instructions in section “Knowledge andDownloads – Documentation – Additional Information: Technical Section; Technical Explications” |
Rated voltage EN (Ex e II) | 550V | Rated current (Ex e II) | 50A |
Power loss, per pole (potential) | 1.819W | Rated current I<sub>N</sub> for specified power loss | 57A |
Resistance value for specified, current-dependent power loss | 0.001Ω | Connection technology | Push-in CAGE CLAMP? |
Actuation type | Operating tool | Connectable conductor materials | Copper |
Nominal cross-section | 10 mm2 | Solid conductor | 0.5 … 16?mm2?/ 20 … 6?AWG |
Solid conductor; push-in termination | 4 … 16?mm2?/ 14 … 6?AWG | Fine-stranded conductor | 0.5 … 16?mm2?/ 20 … 6?AWG |
Fine-stranded conductor; with insulated ferrule | 0.5 … 10?mm2?/ 20 … 8?AWG | Fine-stranded conductor; with ferrule; push-in termination | 4 … 10?mm2?/ 12 … 8?AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.AWG specifications were converted according to IEC. | Strip length | 17 … 19?mm?/ 0.67 … 0.75?inches |
Wiring direction | Front-entry wiring | Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 | Spectrum/Installation location | Service life test, Category?1, Class?A/B |
Function test with noise-like vibration | Test passed according to Section 8 of the standard | Frequency | f1= 5 Hz to f2= 150 Hz |
Acceleration | 5g (highest test level used for all axes) | Test duration per axis | 5 h |
Test directions | X, Y and Z axes | Monitoring for contact faults/interruptions | Passed |
Voltage drop measurement before and after each axis | Passed | Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
Extended test scope: Monitoring for contact faults/interruptions | Passed | Extended test scope: Voltage drop measurement before and after each axis | Passed |
Shock test | Test passed according to Section 10 of the standard | Shock form | Half sine |
Shock duration | 30 ms | Number of shocks per axis | 3 pos. und 3 neg. |
Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice