wago 2010-1309

Selling Points

  • 1Ensures high reliability in hazardous environments.
  • 2Easy and secure wire connection.
  • 3Versatile and space-efficient design.
  • 4Enhanced readability for precise connections.
  • 5Handles high current requirements efficiently.
Product Details
2010-1309
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
3
Total number of potentials
1
Number of levels
1
Number of jumper slots
2
Width
10?mm?/ 0.394?inches
Height
89?mm?/ 3.504?inches
Depth from upper-edge of DIN-rail
36.9?mm?/ 1.453?inches
Depth
43.5 mm / 1.713 inches
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
light gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.391MJ
Weight
23.3g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
eCl@ss 10.0
27-14-11-20
eCl@ss 9.0
27-14-11-20
ETIM 9.0
EC000897
ETIM 8.0
EC000897
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
box
Country of origin
DE
GTIN
4055143645393
Customs tariff number
85369010000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
ATEX: PTB 05 ATEX 1070 U / IECEx: PTB 06.0003U (Ex eb IIC Gb)
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated current
57A
Current at conductor cross-section (max.) mm2
76A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
65A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
65A
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
65A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
65A
Reference hazardous areas
See application instructions in section “Knowledge andDownloads – Documentation – Additional Information: Technical Section; Technical Explications”
Rated voltage EN (Ex e II)
550V
Rated current (Ex e II)
50A
Power loss, per pole (potential)
1.819W
Rated current I<sub>N</sub> for specified power loss
57A
Resistance value for specified, current-dependent power loss
0.001Ω
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
10 mm2
Solid conductor
0.5 … 16?mm2?/ 20 … 6?AWG
Solid conductor; push-in termination
4 … 16?mm2?/ 14 … 6?AWG
Fine-stranded conductor
0.5 … 16?mm2?/ 20 … 6?AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 10?mm2?/ 20 … 8?AWG
Fine-stranded conductor; with ferrule; push-in termination
4 … 10?mm2?/ 12 … 8?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.AWG specifications were converted according to IEC.
Strip length
17 … 19?mm?/ 0.67 … 0.75?inches
Wiring direction
Front-entry wiring
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice