wago 2010-511

Selling Points

  • 1Gray Color: Durable and easy-to-spot gray color.
  • 2Push-in CAGE CLAMP: Secure and efficient connection technology.
  • 332A Rated Current: Handles high electrical currents with reliability.
  • 4Side-entry Wiring: Convenient for various wiring configurations.
  • 5Modular Design: Versatile and expandable for multiple connections.
Product Details
2010-511
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Safety information
According to EN 61984, pluggable connectors without current interrupting capacity must not be mated or unmated when live or under load.
Clamping units
1
Total number of potentials
1
Width
10?mm?/ 0.394?inches
Module width
10?mm?/ 0.394?inches
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.094MJ
Weight
4.9g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
22 (TOPJOB S)
eCl@ss 10.0
27-14-11-51
eCl@ss 9.0
27-14-11-51
ETIM 9.0
EC002021
ETIM 8.0
EC002021
ECCN
NO US CLASSIFICATION
PU (SPU)
50?(25)?pcs
Packaging type
box
Country of origin
DE
GTIN
4050821263722
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Rated voltage (III / 3)
500V
Rated impulse voltage (III / 3)
6kV
Rated current
32A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
4 mm2
Solid conductor
0.5 … 6?mm2?/ 20 … 10?AWG
Solid conductor; push-in termination
4 … 6?mm2?/ 14 … 10?AWG
Fine-stranded conductor
0.5 … 6?mm2?/ 20 … 10?AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 4?mm2?/ 20 … 12?AWG
Fine-stranded conductor; with ferrule; push-in termination
4?mm2?/ 18?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
11 … 13?mm?/ 0.43 … 0.51?inches
Number of poles
1
Wiring direction
Side-entry wiring
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice