Product Model

2022-103/123-000

In Stock
Last updated: 2025/4/19
wago 2022-103/123-000

Selling Points

  • 1Lateral Locking Lever: Secure and reliable connection with a lateral locking lever.
  • 25.2mm Pin Spacing: Precise and efficient terminal block design.
  • 33-Pole Design: Suitable for various applications with a 3-pole configuration.
  • 42.5mm² Capacity: Handles up to 2.5mm² current with ease.
  • 5Push-in CAGE CLAMP: Fast, vibration-proof, and maintenance-free spring pressure connection technology.
Product Details
2022-103/123-000
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Safety information
According to EN 61984, pluggable connectors without current interrupting capacity must not be mated or unmated when live or under load.
Clamping units
3
Total number of potentials
3
Width
15.6?mm?/ 0.614?inches
Height
48.9?mm?/ 1.925?inches
Depth
27.2?mm?/ 1.071?inches
Module width
5.2?mm?/ 0.205?inches
Variable coding
Yes
Marking level
Side marking
Anti-rotation protection
Yes
Contact type (pluggable connector)
Female connector/socket
Connector (connection type)
for conductor
Mismating protection
No
Plugging without loss of pin spacing
Yes
Locking of plug-in connection
Locking lever
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.202MJ
Weight
10.9g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
18 (X-COM-System)
eCl@ss 10.0
27-14-11-06
eCl@ss 9.0
27-14-11-06
ETIM 9.0
EC001284
ETIM 8.0
EC001284
ECCN
NO US CLASSIFICATION
PU (SPU)
100?pcs
Packaging type
Box
Country of origin
DE
GTIN
4050821090052
Customs tariff number
8536694040
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 61984
Rated voltage (III / 3)
690V
Rated impulse voltage (III / 3)
6kV
Rated current
24A
Current at conductor cross-section (max.) mm2
32A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
20A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
20A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
20A
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm2
Solid conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Solid conductor; push-in termination
0.75 … 4?mm2?/ 18 … 12?AWG
Fine-stranded conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5?mm2?/ 22 … 14?AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5?mm2?/ 18 … 14?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12?mm?/ 0.39 … 0.47?inches
Number of poles
3
Wiring direction
Front-entry wiring