Product Model
2022-2231

Selling Points
- 1Connect multiple conductors easily with the WAGO 2022-2231 terminal blocks.
- 2Designed for DIN-rail 35 x 15 and 35 x 7.5 mounting, ensuring versatile installation options.
- 3Securely connect conductors with the reliable Push-in CAGE CLAMP technology.
- 4Available in a durable gray color for easy identification in industrial settings.
- 5Comes with a marker carrier for clear labeling and organization of connections.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Safety information | A separator plate (Item No. 209-191) or a 10 mm end stop (Item No. 249-117) must be placed at the end of a WAGO X-COM?-SYSTEM terminal strip. | Clamping units | 2 |
Female plug slots | 2 | Total number of potentials | 2 |
Number of levels | 2 | Number of jumper slots | 4 |
Width | 5.2?mm?/ 0.205?inches | Height | 80.1?mm?/ 3.154?inches |
Depth from upper-edge of DIN-rail | 61.4?mm?/ 2.417?inches | Potential Marking | L/L |
Design | horizontal type | Mounting type | DIN-35 rail |
Marking level | Side marking | Note (material data) | Information on material specifications can be found here |
Color | gray | Material group | I |
Insulation material (main housing) | Polyamide (PA66) | Flammability class per UL94 | V0 |
Fire load | 0.267MJ | Weight | 12g |
Processing temperature | -35 … +85?°C | Continuous operating temperature | -60 … +105?°C |
Product Group | 18 (X-COM-System) | eCl@ss 10.0 | 27-14-11-20 |
eCl@ss 9.0 | 27-14-11-20 | ETIM 9.0 | EC000897 |
ETIM 8.0 | EC000897 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 50?pcs | Packaging type | Box |
Country of origin | CN | GTIN | 4055143089005 |
Customs tariff number | 85366990990 | RoHS Compliance Status | Compliant,No Exemption |
Ratings per | IEC/EN 60947-7-1 | Rated voltage (III / 3) | 690V |
Rated impulse voltage (III / 3) | 6kV | Rated current | 24A |
Current at conductor cross-section (max.) mm2 | 28A | Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 |
Approvals per | CSA 22.2 No 158 | Rated voltage UL (Use Group B) | 600V |
Rated current UL (Use Group B) | 20A | Rated voltage UL (Use Group C) | 600V |
Rated current UL (Use Group C) | 20A | Rated voltage CSA (Use Group C) | 600V |
Rated current CSA (Use Group C) | 20A | Power loss, per pole (potential) | 0.766W |
Rated current I<sub>N</sub> for specified power loss | 24A | Resistance value for specified, current-dependent power loss | 0.001Ω |
Connection technology | Push-in CAGE CLAMP? | Actuation type | Operating tool |
Connectable conductor materials | Copper | Nominal cross-section | 2.5 mm2 |
Solid conductor | 0.25 … 4?mm2?/ 22 … 12?AWG | Solid conductor; push-in termination | 0.75 … 4?mm2?/ 18 … 12?AWG |
Fine-stranded conductor | 0.25 … 4?mm2?/ 22 … 12?AWG | Fine-stranded conductor; with insulated ferrule | 0.25 … 2.5?mm2?/ 22 … 14?AWG |
Fine-stranded conductor; with ferrule; push-in termination | 1 … 2.5?mm2?/ 18 … 14?AWG | Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. |
Strip length | 10 … 12?mm?/ 0.39 … 0.47?inches | Wiring direction | Front-entry wiring |
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 | Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
Spectrum/Installation location | Service life test, Category?1, Class?A/B | Function test with noise-like vibration | Test passed according to Section 8 of the standard |
Frequency | f1= 5 Hz to f2= 150 Hz | Acceleration | 5g (highest test level used for all axes) |
Test duration per axis | 5 h | Test directions | X, Y and Z axes |
Monitoring for contact faults/interruptions | Passed | Voltage drop measurement before and after each axis | Passed |
Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard | Extended test scope: Monitoring for contact faults/interruptions | Passed |
Extended test scope: Voltage drop measurement before and after each axis | Passed | Shock test | Test passed according to Section 10 of the standard |
Shock form | Half sine | Shock duration | 30 ms |
Number of shocks per axis | 3 pos. und 3 neg. | Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice