wago 2022-2257

Selling Points

  • 1Utilizes Push-in CAGE CLAMP spring connections for fast, vibration-proof, and maintenance-free connections.
  • 2Mounts on DIN-35 rail (35 x 15 / 35 x 7.5) for easy installation and space efficiency.
  • 3Meets ROHS standards and is suitable for Ex e II applications, ensuring high safety levels.
  • 4Supports wire sizes from 0.25mm² to 4mm² or #22AWG to #12AWG, accommodating various conductor types.
  • 5Features a gray housing with marker carrier and side marking slots labeled "PE/L" for easy identification and organization.
Product Details
2022-2257
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Safety information
A separator plate (Item No. 209-191) or a 10 mm end stop (Item No. 249-117) must be placed at the end of a WAGO X-COM?-SYSTEM terminal strip.
Clamping units
2
Female plug slots
2
Total number of potentials
2
Number of levels
2
Number of jumper slots
4
Width
5.2?mm?/ 0.205?inches
Height
80.1?mm?/ 3.154?inches
Depth from upper-edge of DIN-rail
61.4?mm?/ 2.417?inches
Potential Marking
PE/L
Design
horizontal type
Mounting type
DIN-35 rail
Marking level
Side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.267MJ
Weight
15.1g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
18 (X-COM-System)
eCl@ss 10.0
27-14-11-41
eCl@ss 9.0
27-14-11-41
ETIM 9.0
EC000901
ETIM 8.0
EC000901
ECCN
NO US CLASSIFICATION
PU (SPU)
50?pcs
Packaging type
Box
Country of origin
DE
GTIN
4045454994792
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60947-7-1
Rated voltage (III / 3)
690V
Rated impulse voltage (III / 3)
6kV
Rated current
24A
Current at conductor cross-section (max.) mm2
28A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
20A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
20A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
20A
Power loss, per pole (potential)
0.766W
Rated current I<sub>N</sub> for specified power loss
24A
Resistance value for specified, current-dependent power loss
0.001Ω
Connection technology
Push-in CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
2.5 mm2
Solid conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Solid conductor; push-in termination
0.75 … 4?mm2?/ 18 … 12?AWG
Fine-stranded conductor
0.25 … 4?mm2?/ 22 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5?mm2?/ 22 … 14?AWG
Fine-stranded conductor; with ferrule; push-in termination
1 … 2.5?mm2?/ 18 … 14?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
10 … 12?mm?/ 0.39 … 0.47?inches
Wiring direction
Front-entry wiring
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice