wago 2104-1201

Selling Points

  • 1Efficient DIN-Rail Mounting: Designed for easy installation on DIN-35 rail (35 x 15 and 35 x 7.5 mm).
  • 2High Current Rating: Supports up to 32A current and 40A for specific configurations.
  • 3Ex-Approved for Safety: Meets ATEX, IECEx, and UL standards for hazardous environments.
  • 4Push-in Cage Clamp Technology: Connects solid and fine-stranded conductors with ferrules effortlessly.
  • 5Versatile Wire Compatibility: Accommodates wire sizes from 0.5 mm² to 6 mm² or #20AWG to #10AWG.
Product Details
2104-1201
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
2
Total number of potentials
1
Number of levels
1
Number of jumper slots
2
Width
6.2?mm?/ 0.244?inches
Height
70?mm?/ 2.756?inches
Depth from upper-edge of DIN-rail
32.9?mm?/ 1.295?inches
Depth
39.5 mm / 1.555 inches
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.209MJ
Actuator color
orange
Weight
10.3g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
ETIM 9.0
EC000897
ETIM 8.0
EC000897
ECCN
NO US CLASSIFICATION
PU (SPU)
50?pcs
Packaging type
Box
Country of origin
PL
GTIN
4055143992282
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
ATEX: PTB 20 ATEX 1006 U / IECEx: PTB 20.0012U (Ex eb IIC Gb)
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated current
32A
Current at conductor cross-section (max.) mm2
40A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Approvals per
CSA 22.2 No 158
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
30A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
30A
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
30A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
30A
Reference hazardous areas
See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Rated voltage EN (Ex e II)
550V
Rated current (Ex e II)
30A
Power loss, per pole (potential)
1.362W
Rated current I<sub>N</sub> for specified power loss
32A
Resistance value for specified, current-dependent power loss
0.001Ω
Connection technology
Push-in CAGE CLAMP?
Actuation type
Lever
Connectable conductor materials
Copper
Nominal cross-section
4 mm2
Solid conductor
0.5 … 6?mm2?/ 20 … 10?AWG
Solid conductor; push-in termination
1.5 … 6?mm2?/ 14 … 10?AWG
Fine-stranded conductor
0.5 … 6?mm2?/ 20 … 10?AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 4?mm2?/ 20 … 12?AWG
Fine-stranded conductor; with ferrule; push-in termination
1.5 … 4?mm2?/ 18 … 12?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
11 … 13?mm?/ 0.43 … 0.51?inches
Wiring direction
Front-entry wiring
Actuation type 2
Operating tool

Specifications may be subject to change without notice