Product Model
2201-1303

Selling Points
- 1Connects three conductors with a push-button for easy operation.
- 2Suitable for hazardous environments, ensuring safety and reliability.
- 3Designed for DIN-rail 35 x 15 and 35 x 7.5, providing flexible installation options.
- 4Allows for easy testing and verification of connections.
- 5Secure and efficient connection method for solid and fine-stranded conductors.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 3 | Total number of potentials | 1 |
Number of levels | 1 | Number of jumper slots | 2 |
Width | 4.2?mm?/ 0.165?inches | Height | 59.2?mm?/ 2.33?inches |
Depth from upper-edge of DIN-rail | 32.9?mm?/ 1.295?inches | Depth | 39.5 mm / 1.555 inches |
Mounting type | DIN-35 rail | Marking level | Center/side marking |
Note (material data) | Information on material specifications can be found here | Color | red |
Material group | I | Insulation material (main housing) | Polyamide (PA66) |
Flammability class per UL94 | V0 | Fire load | 0.129MJ |
Actuator color | orange | Weight | 5g |
Processing temperature | -35 … +85?°C | Continuous operating temperature | -60 … +105?°C |
ETIM 9.0 | EC000897 | ETIM 8.0 | EC000897 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 100?pcs |
Packaging type | Box | Country of origin | DE |
GTIN | 4066966413861 | Customs tariff number | 85369010000 |
RoHS Compliance Status | Compliant,No Exemption | Ratings per | ATEX: PTB 18 ATEX 1004 U / IECEx: PTB 18.0011U (Ex eb IIC Gb) |
Rated voltage (III / 3) | 800V | Rated impulse voltage (III / 3) | 8kV |
Rated current | 17.5A | Current at conductor cross-section (max.) mm2 | 24A |
Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 | Approvals per | CSA 22.2 No 158 |
Rated voltage UL (Use Group B) | 600V | Rated current UL (Use Group B) | 15A |
Rated voltage UL (Use Group C) | 600V | Rated current UL (Use Group C) | 15A |
Rated voltage CSA (Use Group B) | 600V | Rated current CSA (Use Group B) | 15A |
Rated voltage CSA (Use Group C) | 600V | Rated current CSA (Use Group C) | 15A |
Reference hazardous areas | See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications” | Rated voltage EN (Ex e II) | 550V |
Rated current (Ex e II) | 17.5A | Power loss, per pole (potential) | 0.771W |
Rated current I<sub>N</sub> for specified power loss | 18A | Resistance value for specified, current-dependent power loss | 0.002Ω |
Connection technology | Push-in CAGE CLAMP? | Actuation type | Push-button |
Connectable conductor materials | Copper | Nominal cross-section | 1.5 mm2 |
Solid conductor | 0.25 … 2.5?mm2?/ 22 … 14?AWG | Solid conductor; push-in termination | 0.75 … 2.5?mm2?/ 18 … 14?AWG |
Fine-stranded conductor | 0.25 … 2.5?mm2?/ 22 … 14?AWG | Fine-stranded conductor; with insulated ferrule | 0.25 … 1.5?mm2?/ 22 … 16?AWG |
Fine-stranded conductor; with ferrule; push-in termination | 0.75 … 1.5?mm2?/ 18 … 16?AWG | Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. |
Strip length | 9 … 11?mm?/ 0.35 … 0.43?inches | Wiring direction | Front-entry wiring |
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 | Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
Spectrum/Installation location | Service life test, Category?1, Class?A/B | Function test with noise-like vibration | Test passed according to Section 8 of the standard |
Frequency | f1= 5 Hz to f2= 150 Hz | Acceleration | 5g (highest test level used for all axes) |
Test duration per axis | 5 h | Test directions | X, Y and Z axes |
Monitoring for contact faults/interruptions | Passed | Voltage drop measurement before and after each axis | Passed |
Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard | Extended test scope: Monitoring for contact faults/interruptions | Passed |
Extended test scope: Voltage drop measurement before and after each axis | Passed | Shock test | Test passed according to Section 10 of the standard |
Shock form | Half sine | Shock duration | 30 ms |
Number of shocks per axis | 3 pos. und 3 neg. | Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice