wago 2206-1621

Selling Points

  • 1Compact Design: Ideal for DIN-rail mounting with dimensions of H96.3mm x W7.5mm x D59mm.
  • 2High Current Rating: Supports up to 10A (IEC) and 15A (UL/CSA) for reliable power distribution.
  • 3Versatile Conductor Compatibility: Compatible with 0.5mm² to 10mm² fine stranded or solid conductors, as well as #20AWG to #8AWG.
  • 4Enhanced Safety Features: Equipped with a pivoting fuse holder and push-button actuation for easy operation and blown fuse indication by LED.
  • 5Durable Construction: Made from high-quality polyamide (PA66) material, ensuring long-lasting performance in harsh environments.
Product Details
2206-1621
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
2
Total number of potentials
1
Number of levels
1
Width
7.5?mm?/ 0.295?inches
Height
96.3?mm?/ 3.791?inches
Depth from upper-edge of DIN-rail
59?mm?/ 2.323?inches
Mounting type
DIN-35 rail
Marking level
Center/side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.474MJ
Actuator color
orange
Weight
24.9g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
ETIM 9.0
EC000899
ETIM 8.0
EC000899
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
Box
Country of origin
PL
GTIN
4066966309966
Customs tariff number
85369095000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60947-7-3
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated current
10A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Ratings (note)
Electrical ratings are given by the fuse.
Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
15A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
15A
Power loss P<sub>l</sub> max. overload and short-circuit protection (individual arrangement)
1.6W
Power loss P<sub>l</sub> max. overload and short-circuit protection (group arrangement)
1.6W
Power loss P<sub>l</sub> max. short-circuit protection (individual arrangement)
2.5W
Power loss P<sub>l</sub> max. short-circuit protection (group arrangement)
2.5W
Fuse receptacle
pivoting
Fuse type
Cylindrical fuse; 5 x 30 mm
Connection technology
Push-in CAGE CLAMP?
Actuation type
Push-button
Connectable conductor materials
Copper
Nominal cross-section
6 mm2
Solid conductor
0.5 … 10?mm2?/ 20 … 8?AWG
Solid conductor; push-in termination
1 … 10?mm2?/ 14 … 8?AWG
Fine-stranded conductor
0.5 … 10?mm2?/ 20 … 8?AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 6?mm2?/ 20 … 10?AWG
Fine-stranded conductor; with ferrule; push-in termination
2.5 … 6?mm2?/ 16 … 10?AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
13 … 15?mm?/ 0.51 … 0.59?inches
Wiring direction
Front-entry wiring

Specifications may be subject to change without notice