Product Model
2206-8031/000-053

Selling Points
- 1Designed for hazardous areas with integrated end plate.
- 2Easy and secure wire connections.
- 3Compatible with DIN-rail 35 x 15 and 35 x 7.5 mm.
- 4Supports wire sizes from 0.5mm² to 10mm² or #20AWG to #8AWG.
- 5Rated for currents of 41A and 57A.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 7 | Total number of potentials | 1 |
Number of levels | 1 | Number of jumper slots | 2 |
Width | 9?mm?/ 0.354?inches | Height | 73.8?mm?/ 2.905?inches |
Depth from upper-edge of DIN-rail | 32.9?mm?/ 1.295?inches | Mounting type | DIN-35 rail |
Marking level | Center/side marking | Note (material data) | Information on material specifications can be found here |
Color | dark gray/yellow | Material group | I |
Insulation material (main housing) | Polyamide (PA66) | Flammability class per UL94 | V0 |
Clamping spring material | Chrome-nickel spring steel (CrNi) | Contact plating | Tin |
Fire load | 0.369MJ | Actuator color | orange |
Weight | 16.3g | Processing temperature | -35 … +85?°C |
Continuous operating temperature | -60 … +105?°C | ETIM 9.0 | EC000897 |
ETIM 8.0 | EC000897 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 12?pcs | Packaging type | Box |
Country of origin | DE | GTIN | 4066966257250 |
Customs tariff number | 85369010000 | RoHS Compliance Status | Compliant,No Exemption |
Ratings per | IEC/EN 60947-7-1 | Rated voltage (III / 3) | 800V |
Rated impulse voltage (III / 3) | 8kV | Rated current | 41A |
Current at conductor cross-section (max.) mm2 | 57A | Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 |
Power loss, per pole (potential) | 1.311W | Rated current I<sub>N</sub> for specified power loss | 41A |
Resistance value for specified, current-dependent power loss | 0.001Ω | Connection type 1 | Input |
Connection technology | Push-in CAGE CLAMP? | Total number of connection points | 1 |
Actuation type | Push-button | Connectable conductor materials | Copper |
Nominal cross-section | 6 mm2 | Solid conductor | 0.5 … 10?mm2?/ 20 … 8?AWG |
Solid conductor; push-in termination | 2.5 … 10?mm2?/ 14 … 8?AWG | Fine-stranded conductor | 0.5 … 10?mm2?/ 20 … 8?AWG |
Fine-stranded conductor; with insulated ferrule | 0.5 … 6?mm2?/ 20 … 10?AWG | Fine-stranded conductor; with ferrule; push-in termination | 2.5 … 6?mm2?/ 16 … 10?AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. | Strip length | 13 … 15?mm?/ 0.51 … 0.59?inches |
Wiring direction | Front-entry wiring | Connection type 2 | Output |
Connection technology 2 | Push-in CAGE CLAMP? | Number of connection points 2 | 6 |
Nominal cross-section 2 | 1.5?mm2 | Solid conductor 2 | 0.25 … 2.5?mm2?/ 22 … 14?AWG |
Solid conductor; push-in termination 2 | 0.75 … 2.5?mm2?/ 18 … 14?AWG | Fine-stranded conductor 2 | 0.25 … 2.5?mm2?/ 22 … 14?AWG |
Fine-stranded conductor; with insulated ferrule 2 | 0.25 … 1.5?mm2?/ 22 … 16?AWG | Fine-stranded conductor; with ferrule; push-in termination; 2 | 0.75 … 1.5?mm2?/ 18 … 16?AWG |
Strip length 2 | 9 … 11?mm?/ 0.35 … 0.43?inches | Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 | Spectrum/Installation location | Service life test, Category?1, Class?A/B |
Function test with noise-like vibration | Test passed according to Section 8 of the standard | Frequency | f1= 5 Hz to f2= 150 Hz |
Acceleration | 5g (highest test level used for all axes) | Test duration per axis | 5 h |
Test directions | X, Y and Z axes | Monitoring for contact faults/interruptions | Passed |
Voltage drop measurement before and after each axis | Passed | Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
Extended test scope: Monitoring for contact faults/interruptions | Passed | Extended test scope: Voltage drop measurement before and after each axis | Passed |
Shock test | Test passed according to Section 10 of the standard | Shock form | Half sine |
Shock duration | 30 ms | Number of shocks per axis | 3 pos. und 3 neg. |
Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice