Product Model

221-483

In Stock
Last updated: 2025/4/18
wago 221-483

Selling Points

  • 1Pull the lever up, insert a conductor, and push the lever back down for quick and easy termination.
  • 2Suitable for devices with higher levels of power consumption, up to 440V.
  • 3Meets ATEX (Ex 2 II G) and IECEx (Ex eb IIC Gb) Zone 1, 2 standards for hazardous locations.
  • 4Terminates conductors from 0.14 to 4 mm², including solid, stranded, and fine-stranded wires.
  • 5Transparent housing with light gray levers, operating from -55°C to +105°C.
Product Details
221-483
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Safety management note
NOTICE: Observe installation and safety instructions!Only to be used by electricians!Do not work under voltage/load!Use only for proper use!Observe national regulations/standards/guidelines!Observe technical specifications for the products!Observe the number of permissible potentials!Do not use damaged/dirty components!Observe conductor types, cross-sections and strip lengths!Insert conductor until it hits the product‘s backstop!Use original accessories!To be sold only with installation instructions!
Safety information
The permissible operating voltage of the connector with carrier (440?V or 275?V) depends on the mounting type.
Safety information 2
Only approved in conjunction with a mounting carrier (221-501). Other carriers are possible, see certificate/file. The connectors must be installed in an enclosure meeting the requirements of a recognized protection type per EN 60079-0, GB/T 3836.1 Section 1 or EN 60079-31, GB/T 3836.31. When installing the connectors in an enclosure of protection type “e” (increased safety per EN 60079-7, GB/T 3836.3), the clearances and creepage distances of Table 2 for this standard must be observed. See point 1 for the use of accessories. The connectors can be used both in Group II and Group I, as the standard requirements are identical in this case.The use of these components requires a new assessment by a notified certification agency.
Clamping units
3
Total number of potentials
1
Width
18.8?mm?/ 0.74?inches
Height
8.4 mm / 0.327 inches
Depth
18.6 mm / 0.732 inches
Note (material data)
Information on material specifications can be found here
Color
transparent
Material group
IIIa
Insulation material (main housing)
Polycarbonate (PC)
Flammability class per UL94
V2
Fire load
0.064MJ
Actuator color
light gray
Weight
2.7g
Ambient temperature (storage)
-40 … +60 °C
Continuous operating temperature
-55 … +105?°C
eCl@ss 10.0
27-14-11-04
eCl@ss 9.0
27-14-11-04
ETIM 9.0
EC000446
ETIM 8.0
EC000446
ECCN
NO US CLASSIFICATION
PU (SPU)
500?(50)?pcs
Packaging type
box
Country of origin
DE
GTIN
4055143837347
Customs tariff number
85369010000
RoHS Compliance Status
Compliant,No Exemption
Approvals per
UL 60079
Rated voltage UL (Use Group C)
440V
Rated current UL (Use Group C)
20A
Ratings per
ATEX: PTB 18 ATEX 1019 U / IECEx: PTB 18.0045U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
440V
Rated current (Ex e II)
32A
Connection technology
CAGE CLAMP?
Actuation type
Lever
Connectable conductor materials
Copper
Nominal cross-section
4 mm2 / 12 AWG
Solid conductor
0.2 … 4?mm2?/ 24 … 12?AWG
Stranded conductor
0.2 … 4?mm2?/ 24 … 12?AWG
Fine-stranded conductor
0.14 … 4?mm2?/ 24 … 12?AWG
Strip length
11?mm?/ 0.43?inches
Wiring direction
Side-entry wiring

Specifications may be subject to change without notice