Product Model

231-639/109-000

In Stock
Last updated: 2025/4/18
wago 231-639/109-000

Selling Points

  • 1Universal Connection: Connects all conductor types with ease.
  • 2CAGE CLAMP Actuation: Simplifies cable pre-assembly and on-unit wiring.
  • 3Anti-Rotation Protection: Ensures secure connections with anti-rotation protection.
  • 4High Current Rating: Supports up to 12A rated current (IEC/EN) and 15A (UL/CSA).
  • 5Durable Design: Constructed with electrocopper contacts and polyamide insulation.
Product Details
231-639/109-000
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Safety information
TheMCS – MULTI CONNECTION SYSTEMincludes connectors without breaking capacity in accordance with DIN EN 61984. When used as intended, these connectors must not be connected/disconnected when live or under load.When used as intended, these connectors must not be connected/disconnected when live or under load. The circuit design should ensure header pins, which can be touched, are not live when unmated.
Variants:
Other pole numbers
Clamping units
9
Total number of potentials
9
Number of connection types
1
Number of levels
1
Pin spacing
5.08?mm?/ 0.2?inches
Width
55.62?mm?/ 2.19?inches
Height
14.3?mm?/ 0.563?inches
Depth
27.5?mm?/ 1.083?inches
Variable coding
Yes
Anti-rotation protection
Yes
Contact type (pluggable connector)
Male connector/plug
Connector (connection type)
for conductor
Mismating protection
No
Plugging without loss of pin spacing
No
Locking of plug-in connection
Threaded flange
Note (material data)
Information on material specifications can be found here
Color
orange
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Clamping spring material
Chrome-nickel spring steel (CrNi)
Contact material
Electrolytic copper (ECu)
Contact plating
Tin
Fire load
0.242MJ
Weight
14.6g
Limit temperature range
-60 … +100?°C
Processing temperature
-35 … +60?°C
Product Group
3 (Multi Conn. System)
eCl@ss 10.0
27-44-03-09
eCl@ss 9.0
27-44-03-09
ETIM 9.0
EC002638
ETIM 8.0
EC002638
ECCN
NO US CLASSIFICATION
PU (SPU)
25?pcs
Packaging type
box
Country of origin
DE
GTIN
4045454029227
Customs tariff number
85366930000
CAS-No.
7439-92-1
REACH Candidate List Substance
Lead
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
6(c)
SCIP notification number (Austria)
ff23dfc3-240b-4162-af34-05c212df53d6
SCIP notification number (Belgium)
4e41e86f-81e0-4c41-8b41-66c36ec13443
SCIP notification number (Bulgaria)
1360b626-0f55-4b6e-9bb3-40a1b85470bd
SCIP notification number (Czech Republic)
f51b881d-57ec-4528-b766-fa924b368250
SCIP notification number (Denmark)
4be1c7ea-1514-4dc8-834e-44794b51cdc2
SCIP notification number (Finland)
fb702b01-0dae-4923-93f4-fe9fad16b2b8
SCIP notification number (France)
a3b70b8f-c0eb-4ec8-97f0-53a7c1e402cf
SCIP notification number (Germany)
c2b9bfb0-b0da-4228-b7e2-2e675a28f9aa
SCIP notification number (Hungary)
60f86378-ec52-4f79-b8e1-0d6cba77061b
SCIP notification number (Italy)
6d0f54dc-e55a-42a5-a681-d50e1afce817
SCIP notification number (Netherlands)
cf692da3-fee0-485d-92f6-86c1c8377e16
SCIP notification number (Poland)
89079025-9275-43bb-bce0-d6aa8c7591dc
SCIP notification number (Romania)
d279d940-bc4f-40e4-818b-7981b299d740
SCIP notification number (Sweden)
e9c0b31f-ec0a-4b29-abf0-0c089396e335
Ratings per
IEC/EN 60664-1
Rated voltage (III / 3)
320V
Rated impulse voltage (III / 3)
4kV
Rated voltage (III/2)
320V
Rated surge voltage (III/2)
4kV
Nominal voltage (II/2)
630V
Rated surge voltage (II/2)
4kV
Rated current
12A
Legend (ratings)
(III / 2) ? Overvoltage category III / Pollution degree 2
Approvals per
CSA
Rated voltage UL (Use Group B)
300V
Rated current UL (Use Group B)
15A
Rated voltage UL (Use Group D)
300V
Rated current UL (Use Group D)
10A
Rated voltage (UL 1977)
600V
Rated current UL 1977
15A
Rated voltage CSA (Use Group B)
300V
Rated current CSA (Use Group B)
15A
Rated voltage CSA (Use Group D)
300V
Rated current CSA (Use Group D)
10A
Connection technology
CAGE CLAMP?
Actuation type
Operating tool
Actuation direction 1
Operation parallel to conductor entry
Actuation direction 2
Operation perpendicular to conductor entry
Solid conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Fine-stranded conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 1.5?mm2
Fine-stranded conductor; with uninsulated ferrule
0.25 … 2.5?mm2
Strip length
8 … 9?mm?/ 0.31 … 0.35?inches
Number of poles
9
Conductor entry direction to mating direction
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice