Product Model
2604-3110

Selling Points
- 1High-Quality Connectivity: Reliable and efficient connections ensure optimal performance and safety in electrical installations.
- 2Tool-Free Operation: Intuitive lever operation allows for 100% tool-free handling, simplifying wiring and reducing installation time.
- 3Secure Bonding: Easy-to-use lever closes the clamping unit securely, providing a reliable connection with minimal force.
- 4Multi-Core Cable Handling: Several clamping units can be held open simultaneously, making it convenient for terminating multi-core cables.
- 5Versatile Applications: Suitable for power supplies and automation systems, ensuring secure and stable connections in various applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Variants: | Other pole numbers | Clamping units | 10 |
Total number of potentials | 10 | Number of connection types | 1 |
Number of levels | 1 | Pin spacing | 5?mm?/ 0.197?inches |
Width | 52.4?mm?/ 2.063?inches | Height | 25.3?mm?/ 0.996?inches |
Height from the surface | 21.3?mm?/ 0.839?inches | Depth | 16.7?mm?/ 0.657?inches |
Solder pin length | 4mm | Solder pin dimensions | 0.8 x 1?mm |
Drilled hole diameter with tolerance | 1.3(+0.1)mm | PCB contact | THT |
Solder pin arrangement | over the entire terminal strip (in-line) | Number of solder pins per potential | 2 |
Note (material data) | Information on material specifications can be found here | Color | gray |
Material group | I | Insulation material (main housing) | Polyamide (PA66) |
Flammability class per UL94 | V0 | Clamping spring material | Chrome-nickel spring steel (CrNi) |
Contact material | Electrolytic copper (ECu) | Contact plating | Tin |
Fire load | 0.41MJ | Actuator color | orange |
Weight | 16.4g | Limit temperature range | -60 … +105?°C |
Processing temperature | -35 … +60?°C | Continuous operating temperature | -60 … +105?°C |
eCl@ss 10.0 | 27-44-04-01 | eCl@ss 9.0 | 27-44-04-01 |
ETIM 9.0 | EC002643 | ETIM 8.0 | EC002643 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 30?pcs |
Packaging type | box | Country of origin | PL |
GTIN | 4066966391121 | Customs tariff number | 8536904000 |
RoHS Compliance Status | Compliant,No Exemption | Ratings per | IEC/EN 60664-1 |
Rated voltage (III / 3) | 320V | Rated impulse voltage (III / 3) | 4kV |
Rated voltage (III/2) | 400V | Rated surge voltage (III/2) | 4kV |
Nominal voltage (II/2) | 630V | Rated surge voltage (II/2) | 4kV |
Rated current | 32A | Legend (ratings) | (III / 2) ? Overvoltage category III / Pollution degree 2 |
Approvals per | CSA | Rated voltage UL (Use Group B) | 300V |
Rated current UL (Use Group B) | 20A | Rated voltage UL (Use Group D) | 300V |
Rated current UL (Use Group D) | 10A | Rated voltage CSA (Use Group B) | 300V |
Rated current CSA (Use Group B) | 20A | Rated voltage CSA (Use Group D) | 300V |
Rated current CSA (Use Group D) | 5A | Connection technology | Push-in CAGE CLAMP? |
Actuation type | Lever | Solid conductor | 0.2 … 4?mm2?/ 24 … 12?AWG |
Fine-stranded conductor | 0.2 … 4?mm2?/ 24 … 12?AWG | Fine-stranded conductor; with insulated ferrule | 0.25 … 2.5?mm2 |
Fine-stranded conductor; with uninsulated ferrule | 0.25 … 2.5?mm2 | Fine-stranded conductor; with twin ferrule | 0.25 … 1.5?mm2 |
Strip length | 9 … 11?mm?/ 0.35 … 0.43?inches | Conductor connection direction to PCB | 90° |
Number of poles | 10 | Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 | Spectrum/Installation location | Service life test, Category?1, Class?A/B |
Function test with noise-like vibration | Test passed according to Section 8 of the standard | Frequency | f1= 5 Hz to f2= 150 Hz |
Acceleration | 5g (highest test level used for all axes) | Test duration per axis | 5 h |
Test directions | X, Y and Z axes | Monitoring for contact faults/interruptions | Passed |
Voltage drop measurement before and after each axis | Passed | Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
Extended test scope: Monitoring for contact faults/interruptions | Passed | Extended test scope: Voltage drop measurement before and after each axis | Passed |
Shock test | Test passed according to Section 10 of the standard | Shock form | Half sine |
Shock duration | 30 ms | Number of shocks per axis | 3 pos. und 3 neg. |
Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice