ParameterValueParameterValue
Variants:
Other pole numbers
Clamping units
11
Total number of potentials
11
Number of connection types
1
Number of levels
1
Pin spacing
5?mm?/ 0.197?inches
Width
57.4?mm?/ 2.26?inches
Height
25.3?mm?/ 0.996?inches
Height from the surface
21.3?mm?/ 0.839?inches
Depth
16.7?mm?/ 0.657?inches
Solder pin length
4mm
Solder pin dimensions
0.8 x 1?mm
Drilled hole diameter with tolerance
1.3(+0.1)mm
PCB contact
THT
Solder pin arrangement
over the entire terminal strip (in-line)
Number of solder pins per potential
2
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Clamping spring material
Chrome-nickel spring steel (CrNi)
Contact material
Electrolytic copper (ECu)
Contact plating
Tin
Fire load
0.451MJ
Actuator color
orange
Weight
18g
Limit temperature range
-60 … +105?°C
Processing temperature
-35 … +60?°C
Continuous operating temperature
-60 … +105?°C
eCl@ss 10.0
27-44-04-01
eCl@ss 9.0
27-44-04-01
ETIM 9.0
EC002643
ETIM 8.0
EC002643
ECCN
NO US CLASSIFICATION
PU (SPU)
30?pcs
Packaging type
box
Country of origin
DE
GTIN
4055143564809
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60664-1
Rated voltage (III / 3)
320V
Rated impulse voltage (III / 3)
4kV
Rated voltage (III/2)
400V
Rated surge voltage (III/2)
4kV
Nominal voltage (II/2)
630V
Rated surge voltage (II/2)
4kV
Rated current
32A
Legend (ratings)
(III / 2) ? Overvoltage category III / Pollution degree 2
Approvals per
CSA
Rated voltage UL (Use Group B)
300V
Rated current UL (Use Group B)
20A
Rated voltage UL (Use Group D)
300V
Rated current UL (Use Group D)
10A
Rated voltage CSA (Use Group B)
300V
Rated current CSA (Use Group B)
20A
Rated voltage CSA (Use Group D)
300V
Rated current CSA (Use Group D)
5A
Connection technology
Push-in CAGE CLAMP?
Actuation type
Lever
Solid conductor
0.2 … 4?mm2?/ 24 … 12?AWG
Fine-stranded conductor
0.2 … 4?mm2?/ 24 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 2.5?mm2
Fine-stranded conductor; with uninsulated ferrule
0.25 … 2.5?mm2
Fine-stranded conductor; with twin ferrule
0.25 … 1.5?mm2
Strip length
9 … 11?mm?/ 0.35 … 0.43?inches
Conductor connection direction to PCB
90°
Number of poles
11
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed