Product Model
2616-1103

Selling Points
- 1Easy Installation: Tool-free operation with lever-actuated Push-in CAGE CLAMP connection.
- 2Robust Construction: Made from high-quality materials, ensuring durability and reliability.
- 3Secure Connections: Push-in termination of solid and ferruled conductors for secure connections.
- 4Versatile Use: Suitable for various industrial and automation systems, providing maintenance-free connections.
- 5High Performance: Meets high standards of performance and safety, ensuring optimal functionality in complex electrical networks.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Variants: | Other pole numbers | Clamping units | 3 |
Total number of potentials | 3 | Number of connection types | 1 |
Number of levels | 1 | Pin spacing | 10?mm?/ 0.394?inches |
Width | 32.8?mm?/ 1.291?inches | Height | 37.2?mm?/ 1.465?inches |
Height from the surface | 33.2?mm?/ 1.307?inches | Depth | 32?mm?/ 1.26?inches |
Solder pin length | 4mm | Solder pin dimensions | 1.2 x 1.2?mm |
Drilled hole diameter with tolerance | 1.7(+0.1)mm | PCB contact | THT |
Solder pin arrangement | over the entire terminal strip (in-line) | Number of solder pins per potential | 6 |
Note (material data) | Information on material specifications can be found here | Color | gray |
Material group | I | Insulation material (main housing) | Polyamide (PA66) |
Flammability class per UL94 | V0 | Clamping spring material | Chrome-nickel spring steel (CrNi) |
Contact material | Electrolytic copper (ECu) | Contact plating | Tin |
Fire load | 0.441MJ | Actuator color | orange |
Weight | 30.4g | Limit temperature range | -60 … +105?°C |
Processing temperature | -35 … +60?°C | ETIM 9.0 | EC002643 |
ETIM 8.0 | EC002643 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 40?pcs | Packaging type | Box |
Country of origin | PL | GTIN | 4066966360615 |
Customs tariff number | 85369010000 | RoHS Compliance Status | Compliant,No Exemption |
Ratings per | IEC/EN 60664-1 | Rated voltage (III / 3) | 320V |
Rated impulse voltage (III / 3) | 4kV | Rated voltage (III/2) | 320V |
Rated surge voltage (III/2) | 4kV | Nominal voltage (II/2) | 630V |
Rated surge voltage (II/2) | 4kV | Rated current | 76A |
Legend (ratings) | (III / 2) ? Overvoltage category III / Pollution degree 2 | Approvals per | CSA |
Rated voltage UL (Use Group B) | 300V | Rated current UL (Use Group B) | 72A |
Rated voltage UL (Use Group C) | 150V | Rated current UL (Use Group C) | 72A |
Rated voltage UL (Use Group D) | 300V | Rated current UL (Use Group D) | 10A |
Rated voltage CSA (Use Group B) | 300V | Rated current CSA (Use Group B) | 72A |
Rated voltage CSA (Use Group C) | 150V | Rated current CSA (Use Group C) | 72A |
Rated voltage CSA (Use Group D) | 300V | Rated current CSA (Use Group D) | 72A |
Connection technology | Push-in CAGE CLAMP? | Actuation type | Lever |
Solid conductor | 0.75 … 16?mm2?/ 18 … 4?AWG | Fine-stranded conductor | 0.75 … 25?mm2?/ 18 … 4?AWG |
Fine-stranded conductor; with insulated ferrule | 0.75 … 16?mm2 | Fine-stranded conductor; with uninsulated ferrule | 0.75 … 16?mm2 |
Fine-stranded conductor; with twin ferrule | 0.75 … 6?mm2 | Strip length | 18 … 20?mm?/ 0.71 … 0.79?inches |
Conductor connection direction to PCB | 0° | Number of poles | 3 |
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 | Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
Spectrum/Installation location | Service life test, Category?1, Class?A/B | Function test with noise-like vibration | Test passed according to Section 8 of the standard |
Frequency | f1= 5 Hz to f2= 150 Hz | Acceleration | 5g (highest test level used for all axes) |
Test duration per axis | 5 h | Test directions | X, Y and Z axes |
Monitoring for contact faults/interruptions | Passed | Voltage drop measurement before and after each axis | Passed |
Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard | Extended test scope: Monitoring for contact faults/interruptions | Passed |
Extended test scope: Voltage drop measurement before and after each axis | Passed | Shock test | Test passed according to Section 10 of the standard |
Shock form | Half sine | Shock duration | 30 ms |
Number of shocks per axis | 3 pos. und 3 neg. | Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice