Product Model

2616-3354

In Stock
Last updated: 2025/4/20
wago 2616-3354

Selling Points

  • 1High-quality, durable construction for long-lasting performance.
  • 2Easy-to-use design with quick and secure connections.
  • 3Compatible with a wide range of industrial applications.
  • 4Robust insulation for protection against environmental factors.
  • 5Meets or exceeds industry standards for reliability and safety.
Product Details
2616-3354
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Variants:
Other pole numbers
Clamping units
4
Total number of potentials
4
Number of connection types
1
Number of levels
1
Pin spacing
15?mm?/ 0.591?inches
Width
56.5?mm?/ 2.224?inches
Height
38.2?mm?/ 1.504?inches
Height from the surface
34.2?mm?/ 1.346?inches
Depth
29.4?mm?/ 1.157?inches
Solder pin length
4mm
Solder pin dimensions
1.2 x 1.2?mm
Drilled hole diameter with tolerance
1.7(+0.1)mm
PCB contact
THT
Solder pin arrangement
Over the entire terminal strip (in-line)
Number of solder pins per potential
6
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Clamping spring material
Chrome-nickel spring steel (CrNi)
Contact material
Electrolytic copper (ECu)
Contact plating
Tin
Fire load
0.726MJ
Actuator color
orange
Weight
44g
Limit temperature range
-60 … +105?°C
Processing temperature
-35 … +60?°C
ETIM 9.0
EC002643
ETIM 8.0
EC002643
ECCN
NO US CLASSIFICATION
PU (SPU)
28?pcs
Packaging type
box
Country of origin
PL
GTIN
4055143860543
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60664-1
Rated voltage (III / 3)
800V
Rated impulse voltage (III / 3)
8kV
Rated voltage (III/2)
1000V
Rated surge voltage (III/2)
8kV
Nominal voltage (II/2)
1000V
Rated surge voltage (II/2)
8kV
Rated current
76A
Legend (ratings)
(III / 2) ? Overvoltage category III / Pollution degree 2
Approvals per
CSA
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
66A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
66A
Rated voltage UL (Use Group D)
600V
Rated current UL (Use Group D)
66A
Rated voltage CSA (Use Group B)
300V
Rated current CSA (Use Group B)
72A
Rated voltage CSA (Use Group C)
300V
Rated current CSA (Use Group C)
72A
Rated voltage CSA (Use Group D)
600V
Rated current CSA (Use Group D)
72A
Connection technology
Push-in CAGE CLAMP?
Actuation type
Lever
Solid conductor
0.75 … 16?mm2?/ 18 … 4?AWG
Fine-stranded conductor
0.75 … 25?mm2?/ 18 … 4?AWG
Fine-stranded conductor; with insulated ferrule
0.75 … 16?mm2
Fine-stranded conductor; with uninsulated ferrule
0.75 … 16?mm2
Fine-stranded conductor; with twin ferrule
0.75 … 6?mm2
Strip length
18 … 20?mm?/ 0.71 … 0.79?inches
Conductor connection direction to PCB
90°
Number of poles
4
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice