Product Model
264-236

Selling Points
- 1Ex e II Certified: Meets stringent safety standards for hazardous environments.
- 26-Pole Design: Accommodates 24 wires with 12 clamps on each side.
- 3CAGE CLAMP Connections: Secure and reliable spring connections.
- 4Light Gray Color: Easy to identify and visually appealing.
- 5DIN Rail Mounting: Convenient and space-efficient mounting option.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 24 | Total number of potentials | 6 |
Number of levels | 1 | Width | 76?mm?/ 2.992?inches |
Height from the surface | 22.1?mm?/ 0.87?inches | Depth | 32?mm?/ 1.26?inches |
Module width | 10?mm?/ 0.394?inches | Design | horizontal type |
Mounting type | Mounting flange | Marking level | Center marking |
Note (material data) | Information on material specifications can be found here | Color | light gray |
Material group | I | Insulation material (main housing) | Polyamide (PA66) |
Flammability class per UL94 | V0 | Fire load | 0.74MJ |
Halogen-free | Yes | Weight | 39.6g |
Product Group | 9 (Std Chassis Mt Blocks) | eCl@ss 10.0 | 27-14-11-06 |
eCl@ss 9.0 | 27-14-11-06 | ETIM 9.0 | EC001284 |
ETIM 8.0 | EC001284 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 50?pcs | Packaging type | box |
Country of origin | DE | GTIN | 4044918415705 |
Customs tariff number | 8536904000 | RoHS Compliance Status | Compliant,No Exemption |
Reference hazardous areas | See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications” | Rated voltage EN (Ex e II) | 690V |
Rated current (Ex e II) | 23A | Connection technology | CAGE CLAMP? |
Actuation type | Operating tool | Connectable conductor materials | Copper |
Solid conductor | 0.08 … 2.5?mm2?/ 28 … 12?AWG | Fine-stranded conductor | 0.08 … 2.5?mm2?/ 28 … 12?AWG |
Note (conductor cross-section) | 12 AWG: THHN, THWN | Strip length | 8 … 9?mm?/ 0.31 … 0.35?inches |
Number of poles | 6 | Wiring direction | Front-entry wiring |
Specifications may be subject to change without notice