Selling Points

  • 1Reliable and secure connections with CAGE CLAMP technology.
  • 2Compatible with solid and fine-stranded conductors (1.5 to 16 mm²).
  • 3Supports 7-pole connections with a commoning option.
  • 4Made from high-quality Polyamide (PA66) with a flammability class of V0.
  • 5RoHS compliant and suitable for through-hole technology (THT) PCB contact.
Product Details
2716-157
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Variants:
Other pole numbers
Clamping units
7
Total number of potentials
7
Number of connection types
1
Number of levels
1
Number of jumper slots
1
Pin spacing
10 mm / 0.394 inches
Width
70 mm / 2.756 inches
Height
33.3 mm / 1.311 inches
Height from the surface
28.8 mm / 1.134 inches
Depth
35 mm / 1.378 inches
Solder pin length
4.5mm
Solder pin dimensions
0.95 x 1.2 mm
Drilled hole diameter with tolerance
1.6(+0.1)mm
PCB contact
THT
Solder pin arrangement
over the entire terminal strip (in-line)
Number of solder pins per potential
4
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Clamping spring material
Chrome-nickel spring steel (CrNi)
Contact material
Electrolytic copper (ECu)
Contact plating
Tin
Fire load
1.328MJ
Weight
73.4g
Limit temperature range
-60 … +105 °C
Product Group
4 (Printed Circuit Connectors)
eCl@ss 10.0
27-44-04-01
eCl@ss 9.0
27-44-04-01
ETIM 9.0
EC002643
ETIM 8.0
EC002643
ECCN
NO US CLASSIFICATION
PU (SPU)
12 pcs
Packaging type
Box
Country of origin
PL
GTIN
4045454739393
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60664-1
Rated voltage (III / 3)
320V
Rated impulse voltage (III / 3)
4kV
Rated voltage (III/2)
320V
Rated surge voltage (III/2)
4kV
Nominal voltage (II/2)
630V
Rated surge voltage (II/2)
4kV
Rated current
76A
Legend (ratings)
(III / 2) ? Overvoltage category III / Pollution degree 2
Approvals per
UL 1059
Rated voltage UL (Use Group B)
300V
Rated current UL (Use Group B)
55A
Rated voltage UL (Use Group C)
150V
Rated current UL (Use Group C)
55A
Rated voltage UL (Use Group D)
300V
Rated current UL (Use Group D)
10A
Connection technology
CAGE CLAMP?
Actuation type
Lever
Solid conductor
1.5 … 16 mm2 / 16 … 6 AWG
Fine-stranded conductor
1.5 … 16 mm2 / 16 … 6 AWG
Fine-stranded conductor; with insulated ferrule
1.5 … 10 mm2
Fine-stranded conductor; with uninsulated ferrule
1.5 … 10 mm2
Strip length
12 … 13 mm / 0.47 … 0.51 inches
Conductor connection direction to PCB
30°
Number of poles
7

Specifications may be subject to change without notice