Product Model

2787-2358

In Stock
Last updated: 2025/4/19
wago 2787-2358

Selling Points

  • 1Up to 96% efficiency ensures minimal energy loss and maximum power delivery.
  • 2Configure output voltage and select desired protocols for seamless integration with automation systems.
  • 3Includes TopBoost, PowerBoost, and configurable overload behavior for reliable system operation.
  • 4LED bar chart indicates current output power, overloads, and load reserves, along with optical status indication.
  • 5Suitable for both parallel and series operation, with snap-on communication modules available for enhanced connectivity.
Product Details
2787-2358
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Isolation voltage (pri.-sec., AC)
3,510V
Isolation voltage (pri.-PE, AC)
2,200V
Isolation voltage (sec.-PE)
DC 0.5?kV
Protection class
I
Protection type
IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Short-circuit-protected
Yes
Open-circuit-proof
Yes
Parallel operation
Yes
Series operation
Yes
MTBF
> 800,000 h (per IEC 61709)
Connection type 1
Input/signaling
Connection technology
CAGE CLAMP?
WAGO connector
WAGO 721 Series
Solid conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Fine-stranded conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.25 … 1.5?mm2?/ 20 … 16?AWG
Fine-stranded conductor; with uninsulated ferrule
0.25 … 2.5?mm2?/ 20 … 14?AWG
Strip length
8 … 9?mm?/ 0.31 … 0.35?inches
Connection type 2
Output
Connection technology 2
Push-in CAGE CLAMP?
WAGO connector 2
WAGO 831 Series
Solid conductor 2
0.5 … 10?mm2?/ 20 … 8?AWG
Fine-stranded conductor 2
0.5 … 10?mm2?/ 20 … 8?AWG
Fine-stranded conductor; with insulated ferrule 2
0.5 … 6?mm2
Fine-stranded conductor; with uninsulated ferrule 2
0.5 … 6?mm2
Strip length 2
13 … 15?mm?/ 0.51 … 0.59?inches
Width
120?mm?/ 4.724?inches
Height
130?mm?/ 5.118?inches
Depth from upper-edge of DIN-rail
130?mm?/ 5.118?inches
Note (dimensions)
Height without connector
Mounting type
DIN-35 rail
Weight
2000g
Ambient temperature (operation)
-25 … +70 °C (Device starts at ?40 °C (type-tested))
Ambient temperature (storage)
-40 … +85 °C
Relative humidity
5 … 96?% (no condensation permissible)
Derating
See instruction leaflet
Climatic category
3K3 (per EN 60721)
Operating altitude (max.)
5000m
Conformity marking
CE
Standards/specifications
SEMI F47
ETIM 9.0
EC002540
ETIM 8.0
EC002540
ECCN
NO US CLASSIFICATION
PU (SPU)
1?pcs
Packaging type
Box
Country of origin
CN
GTIN
4066966155891
Customs tariff number
85044083900
RoHS Compliance Status
Compliant,No Exemption
Phases
3
Nominal input voltage [V]
(2 / 3) x AC 400 ... 500V
Input voltage range
3 x AC?340 … 550?V
Nominal mains frequency range
50 … 60?Hz
Input current I<sub>i</sub>
≤?3 x 1.6?A (400 VAC; 48 VDC / 20 A)
Inrush current
≤?15?A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥?20?ms (3 x 400 VAC)
Nominal output voltage [V]
DC?48?V (SELV)
Output voltage range
DC 48 … 56?V?(adjustable)
Default setting
DC?48?V
Nominal output current I<sub>o nom</sub>
20?A (48 VDC)
Nominal output power
960W
Deviation
≤?1?%
Residual ripple
≤?70?mV (peak-to-peak)
Current limitation
1.1 x Io nom(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current mode (other overload behaviors can be set)
PowerBoost
DC?30?A (5?s)
TopBoost
Up to 600 %
Signaling
Digital signal input and output (DI/DO)
Communications
EtherNet/IPTM(2789-9023 Communication Module)
Efficiency (typ.)
96?%
Internal fuse
2 x T 5 A / 500?VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x 16 A (for USA/Canada: 3 x 15 A)