Product Model
280-104

Selling Points
- 1Designed for hazardous environments, ensuring safety and reliability.
- 2Easy and secure connection using the CAGE CLAMP system.
- 3Conveniently mounts on DIN-rail 35 x 15 and 35 x 7.5, saving space.
- 4Easy identification of connections with lateral marker slots.
- 5Supports up to 24 A, making it suitable for demanding electrical applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 2 | Total number of potentials | 1 |
Number of levels | 1 | Width | 5?mm?/ 0.197?inches |
Height | 42.5?mm?/ 1.673?inches | Depth from upper-edge of DIN-rail | 30.5?mm?/ 1.201?inches |
Design | horizontal type | Mounting type | DIN-35 rail |
Marking level | Side marking | Note (material data) | Information on material specifications can be found here |
Color | blue | Material group | I |
Insulation material (main housing) | Polyamide (PA66) | Flammability class per UL94 | V0 |
Fire load | 0.083MJ | Weight | 3.9g |
Processing temperature | -35 … +85?°C | Continuous operating temperature | -60 … +105?°C |
eCl@ss 10.0 | 27-14-11-20 | eCl@ss 9.0 | 27-14-11-20 |
ETIM 9.0 | EC000897 | ETIM 8.0 | EC000897 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 100?pcs |
Packaging type | box | Country of origin | IN |
GTIN | 4045454044503 | Customs tariff number | 8536904000 |
RoHS Compliance Status | Compliant,No Exemption | Ratings per | IEC/EN 60947-7-1 |
Rated voltage (III / 3) | 800V | Rated impulse voltage (III / 3) | 8kV |
Rated current | 24A | Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 |
Approvals per | CSA 22.2 No 158 | Rated voltage UL (Use Group C) | 600V |
Rated current UL (Use Group C) | 20A | Rated voltage CSA (Use Group C) | 600V |
Rated current CSA (Use Group C) | 20A | Power loss, per pole (potential) | 0.766W |
Rated current I<sub>N</sub> for specified power loss | 24A | Resistance value for specified, current-dependent power loss | 0.001Ω |
Connection technology | CAGE CLAMP? | Actuation type | Operating tool |
Connectable conductor materials | Copper | Connectable conductor materials (note) | Terminating Aluminum ConductorsWAGO Spring-Clamp Terminal Blocks are suitable for solid aluminum conductors up to 4 mm2/12 AWG if WAGO “Alu-Plus” Contact Paste249-130is used for termination.“Alu-Plus” Contact Paste Advantages:Automatically destroys the oxide film during clamping.Prevents fresh oxidation at the clamping point.Prevents electrolytic corrosion between aluminum and copper conductors (in the same terminal block).Provides long-term protection against corrosion.Using terminal blocks with CAGE CLAMP?Spring Pressure Connection Technology,aluminum conductors must first be cleaned with a bladeand then immediately inserted into the clamping units filled with “Alu-Plus” contact paste.It is also possible to apply WAGO “Alu-Plus”additionallyon the whole surface of the aluminum conductor before termination.Please note that the nominal currents must be adapted to the reduced conductivity of the aluminum conductors::2.5 mm2 = 16 A4 mm2 = 22 A |
Solid conductor | 0.08 … 2.5?mm2?/ 28 … 12?AWG | Fine-stranded conductor | 0.08 … 2.5?mm2?/ 28 … 12?AWG |
Note (conductor cross-section) | 12 AWG: THHN, THWN | Strip length | 8 … 9?mm?/ 0.31 … 0.35?inches |
Wiring direction | Side-entry wiring |