Product Model
280-601

Selling Points
- 1Secure and reliable connection technology.
- 2Supports up to 800VAC for robust industrial use.
- 3Measuring 1.1 in H x 0.197 in W x 0.197 in D for space-saving installations.
- 4Accepts wire sizes from 28 to 12 AWG.
- 5Front-entry wiring and side marking for straightforward setup.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Clamping units | 2 | Total number of potentials | 1 |
Number of levels | 1 | Width | 5?mm?/ 0.197?inches |
Height | 50?mm?/ 1.969?inches | Depth from upper-edge of DIN-rail | 28?mm?/ 1.102?inches |
Mounting type | DIN-35 rail | Marking level | Side marking |
Note (material data) | Information on material specifications can be found here | Color | gray |
Material group | I | Insulation material (main housing) | Polyamide (PA66) |
Flammability class per UL94 | V0 | Fire load | 0.093MJ |
Weight | 4.8g | Processing temperature | -35 … +85?°C |
Continuous operating temperature | -60 … +105?°C | Product Group | 1 (Rail Mounted Terminal Blocks) |
eCl@ss 10.0 | 27-14-11-20 | eCl@ss 9.0 | 27-14-11-20 |
ETIM 9.0 | EC000897 | ETIM 8.0 | EC000897 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 100?pcs |
Packaging type | box | Country of origin | DE |
GTIN | 4044918465298 | Customs tariff number | 8536904000 |
RoHS Compliance Status | Compliant,No Exemption | Ratings per | IEC/EN 60947-7-1 |
Rated voltage (III / 3) | 800V | Rated impulse voltage (III / 3) | 8kV |
Rated current | 24A | Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 |
Approvals per | CSA 22.2 No 158 | Rated voltage UL (Use Group C) | 600V |
Rated current UL (Use Group C) | 20A | Rated voltage CSA (Use Group C) | 600V |
Rated current CSA (Use Group C) | 24A | Power loss, per pole (potential) | 0.766W |
Rated current I<sub>N</sub> for specified power loss | 24A | Resistance value for specified, current-dependent power loss | 0.001Ω |
Connection technology | CAGE CLAMP? | Actuation type | Operating tool |
Connectable conductor materials | Copper | Connectable conductor materials (note) | Terminating Aluminum ConductorsWAGO Spring-Clamp Terminal Blocks are suitable for solid aluminum conductors up to 4 mm2/12 AWG if WAGO “Alu-Plus” Contact Paste249-130is used for termination.“Alu-Plus” Contact Paste Advantages:Automatically destroys the oxide film during clamping.Prevents fresh oxidation at the clamping point.Prevents electrolytic corrosion between aluminum and copper conductors (in the same terminal block).Provides long-term protection against corrosion.Using terminal blocks with CAGE CLAMP?Spring Pressure Connection Technology,aluminum conductors must first be cleaned with a bladeand then immediately inserted into the clamping units filled with “Alu-Plus” contact paste.It is also possible to apply WAGO “Alu-Plus”additionallyon the whole surface of the aluminum conductor before termination.Please note that the nominal currents must be adapted to the reduced conductivity of the aluminum conductors::2.5 mm2 = 16 A4 mm2 = 22 A |
Solid conductor | 0.08 … 2.5?mm2?/ 28 … 12?AWG | Fine-stranded conductor | 0.08 … 2.5?mm2?/ 28 … 12?AWG |
Note (conductor cross-section) | 12 AWG: THHN, THWN | Strip length | 8 … 9?mm?/ 0.31 … 0.35?inches |
Wiring direction | Front-entry wiring | Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests | DIN EN 61373 (VDE 0115-0106):2011-04 | Spectrum/Installation location | Service life test, Category?1, Class?A/B |
Function test with noise-like vibration | Test passed according to Section 8 of the standard | Frequency | f1= 5 Hz to f2= 150 Hz |
Acceleration | 5g (highest test level used for all axes) | Test duration per axis | 5 h |
Test directions | X, Y and Z axes | Monitoring for contact faults/interruptions | Passed |
Voltage drop measurement before and after each axis | Passed | Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
Extended test scope: Monitoring for contact faults/interruptions | Passed | Extended test scope: Voltage drop measurement before and after each axis | Passed |
Shock test | Test passed according to Section 10 of the standard | Shock form | Half sine |
Shock duration | 30 ms | Number of shocks per axis | 3 pos. und 3 neg. |
Vibration and shock stress for rolling stock equipment | Passed |
Specifications may be subject to change without notice