Product Model
280-944/281-589

Selling Points
- 1High operational reliability and system uptime.
- 2Secure DIN rail mounting for easy installation.
- 3Built-in suppressor diode for overvoltage protection.
- 4Compatible with wire sizes 28 to 14 AWG.
- 5Compact design with dimensions 1.55 in H x 0.39 in W x 2.52 in D.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Nominal operating voltage | DC?24?V | Maximum continuous voltage | DC?28?V |
Rated continuous current | 20A | Nominal discharge current (8/20?μs) (line) | 169?A |
Protection level (8/20?μs) | ≤?DC 59?V | Capacitance | ≤?2.7?nF |
Connections (number) | 4 | Connection technology | CAGE CLAMP? |
Solid conductor | 0.08 … 2.5?mm2?/ 28 … 14?AWG | Fine-stranded conductor | 0.08 … 2.5?mm2?/ 28 … 14?AWG |
Strip length | 8 … 9?mm?/ 0.31 … 0.35?inches | Width | 10?mm?/ 0.394?inches |
Height | 64 mm / 2.52 inches | Depth from upper-edge of DIN-rail | 39.5 mm / 1.555 inches |
Design | with end plate | Mounting type | DIN-35 rail |
Color | gray | Insulation material (main housing) | Polyamide (PA66) |
Material group | I | Flammability class per UL94 | V0 |
Fire load | 0.449MJ | Weight | 13.6g |
Processing temperature | -35 … +85?°C | Product Group | 1 (Rail Mounted Terminal Blocks) |
eCl@ss 10.0 | 27-14-11-27 | eCl@ss 9.0 | 27-14-11-20 |
ETIM 9.0 | EC000903 | ETIM 8.0 | EC000903 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 50?(1)?pcs |
Packaging type | box | Country of origin | DE |
GTIN | 4050821515081 | Customs tariff number | 8536904000 |
CAS-No. | 7439-92-1 | REACH Candidate List Substance | Lead |
RoHS Compliance Status | Compliant,With Exemption | RoHS Exemption | 7(a) |
SCIP notification number (Austria) | 36f60e91-2abb-4a81-84cd-74a8ba6aa843 | SCIP notification number (Belgium) | 0f8ec8aa-0af3-4497-a48d-da77118d1526 |
SCIP notification number (Bulgaria) | eb069abd-bf7e-47ec-8657-1693ff4eca74 | SCIP notification number (Czech Republic) | 21fd1b35-c860-456d-850c-d73758900088 |
SCIP notification number (Finland) | ca267a9c-4b32-466b-a8c0-663a15add461 | SCIP notification number (France) | d598d1e0-adb4-459e-be8d-5cae90f5b70a |
SCIP notification number (Germany) | 590a16fc-cc88-4bb1-a37c-12e6146ef191 | SCIP notification number (Hungary) | 6914987f-c784-442c-88eb-b625c25801e6 |
SCIP notification number (Italy) | f18f81f5-05bc-4454-94f5-a743d85d03b3 | SCIP notification number (Netherlands) | 5b43abe0-4d78-4962-9ec7-cc3bb25dab95 |
SCIP notification number (Poland) | 1178dea2-0ea3-4d4f-bd5c-e005edab72a3 | SCIP notification number (Romania) | e6bb5718-1dff-487b-9f55-1f0839074646 |
SCIP notification number (Sweden) | eb458542-d85b-4b3f-807b-881f72c4b635 |
Specifications may be subject to change without notice