wago 282-120

Selling Points

  • 1DIN-Rail Mounting: Mounts easily on DIN-35 rail (35 x 15 / 35 x 7.5).
  • 2CAGE CLAMP Connections: Securely connects conductors with CAGE CLAMP spring connections.
  • 3Wide Wire Compatibility: Accommodates wire sizes from 0.2mm² to 6mm² (#24AWG to #10AWG).
  • 4High Current Rating: Rated for a current of 10A.
  • 5Gray Color and Compact Design: Gray color with a compact width of 13mm and height of 62mm.
Product Details
282-120
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Clamping units
2
Total number of potentials
2
Number of levels
1
Width
13?mm?/ 0.512?inches
Height
62?mm?/ 2.441?inches
Depth from upper-edge of DIN-rail
56.5?mm?/ 2.224?inches
Design
horizontal type
Mounting type
DIN-35 rail
Marking level
Side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.429MJ
Weight
26.6g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
1 (Rail Mounted Terminal Blocks)
eCl@ss 10.0
27-14-11-16
eCl@ss 9.0
27-14-11-16
ETIM 9.0
EC000899
ETIM 8.0
EC000899
ECCN
NO US CLASSIFICATION
PU (SPU)
40?pcs
Packaging type
box
Country of origin
CN
GTIN
4044918558525
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Rated voltage (III / 3)
500V
Rated impulse voltage (III / 3)
6kV
Rated current
10A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Power loss (max.) P<sub>l (max.)</sub> (note)
When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN?60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
Power loss P<sub>l</sub> max. overload and short-circuit protection (individual arrangement)
2.5W
Power loss P<sub>l</sub> max. overload and short-circuit protection (group arrangement)
2.5W
Power loss P<sub>l</sub> max. short-circuit protection (individual arrangement)
4W
Power loss P<sub>l</sub> max. short-circuit protection (group arrangement)
4W
Fuse receptacle
screwed
Fuse type
Cylindrical fuse; ?" x 1"
Connection technology
CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Solid conductor
0.2 … 6?mm2?/ 24 … 10?AWG
Fine-stranded conductor
0.2 … 6?mm2?/ 24 … 10?AWG
Strip length
12 … 13?mm?/ 0.47 … 0.51?inches
Wiring direction
Side-entry wiring

Specifications may be subject to change without notice