Selling Points
- 1Robust Connectivity: Supports CC-Link protocol for seamless industrial communication.
- 2High Baud Rates: Operates at 156 kBd to 10 MBd for efficient data transfer.
- 3Extended Temperature Range: Suitable for ambient temperatures between -20°C and +60°C.
- 4Compact Design: Measures 3.937 in H x 2.421 in W x 2.831 in D for easy mounting.
- 5Durable Construction: Made from polycarbonate and polyamide 6.6 for long-lasting performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Communications | CC-Link | Device-specific | Operating mode: CC-Link V2.0 (default setting)/V1.1; Advanced cycle setting: 1, 2, 4 (default setting), 8 cycles |
Number of fieldbus nodes on master (max.) | 64 | Transmission rate | 156/10 MBd |
Bus segment length (max.) | 1200 m | Transmission medium (communication/fieldbus) | Shielded Cu cable 2 / 3 x 0.5 mm2 |
Station addresses | 1 … 4 / 4 (default setting) | Number of modules per node (max.) | 64 |
Number of modules without a bus extension (max.) | 64 | Input process image (note) | RX (digital inputs): V1.1: 16, 48, 80, 112 bits; V2.0: 16, 48, 80, 112 bits (1 cycle); V2.0: 16, 80, 144, 208 bits (2 cycles); V2.0: 48, 176, 304, 432 bits (4 cycles); V2.0: 112, 368, 624, 880 bits (8 cycles) and 16 bits per system area; RWr (analog inputs): V1.1: 4, 8, 12, 16 words (16 bits); V2.0: 4, 8, 12, 16 words (1 cycle); V2.0: 8, 16, 24, 32 words (2 cycles); V2.0: 16, 32, 48, 64 words (4 cycles); V2.0: 32, 64, 96, 128 words (8 cycles) |
Output process image (note) | RY (digital outputs): V1.1: 16, 48, 80, 112 bits; V2.0: 16, 48, 80, 112 bits (1 cycle); V2.0: 16, 80, 144, 208 bits (2 cycles); V2.0: 48, 176, 304, 432 bits (4 cycles); V2.0: 112, 368, 624, 880 bits (8 cycles) and 16 bits per system area; RWw (analog outputs): V1.1: 4, 8, 12, 16 words (16 bits); V2.0: 4, 8, 12, 16 words (1 cycle); V2.0: 8, 16, 24, 32 words (2 cycles); V2.0: 16, 32, 48, 64 words (4 cycles); V2.0: 32, 64, 96, 128 words (8 cycles) | Supply voltage (system) | 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP?connection) |
Current consumption (5 V system supply) | 200mA | Total current (system supply) | 1,800mA |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts | Input current (typ.) at nominal load (24?V) | 600mA |
Power supply efficiency (typ.) at nominal load (24 V) | 90% | Isolation | 500 V system/field |
Number of outgoing power jumper contacts | 3 | Current carrying capacity (power jumper contacts) | 10A |
Connection technology: communication/fieldbus | CC-Link: 1 x Male connector; 4-pole | Connection technology: field supply | 6 x CAGE CLAMP? |
Connection technology: system supply | 2 x CAGE CLAMP? | Connection type 1 | System/field supply |
Solid conductor | 0.08 … 2.5 mm2 / 28 … 14 AWG | Fine-stranded conductor | 0.08 … 2.5 mm2 / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches | Connection technology: device configuration | 1 x Male connector; 4-pole |
Width | 61.5 mm / 2.421 inches | Height | 100 mm / 3.937 inches |
Depth | 71.9 mm / 2.831 inches | Depth from upper-edge of DIN-rail | 64.7 mm / 2.547 inches |
Mounting type | DIN-35 rail | Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 2.586MJ | Weight | 148.5g |
Conformity marking | CE | Ambient temperature (operation) | 0 … +55 °C |
Ambient temperature (storage) | -25 … +85 °C | Protection type | IP20 |
Pollution degree | 2 per IEC 61131-2 | Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom | Relative humidity (without condensation) | 95% |
Vibration resistance | per IEC 60068-2-6 | Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2 | EMC emission of interference | per EN 61000-6-4 |
Exposure to pollutants | per IEC 60068-2-42 and IEC 60068-2-43 | Permissible pollutant concentration H<sub>2</sub>S at a relative humidity < 75% | 10ppm |
Permissible pollutant concentration SO <sub> 2 </sub> at a relative humidity < 75% | 25ppm | eCl@ss 10.0 | 27-24-26-07 |
eCl@ss 9.0 | 27-24-26-07 | ETIM 9.0 | EC001603 |
ETIM 8.0 | EC001603 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 1 pcs | Packaging type | Box |
Country of origin | DE | Customs tariff number | 8517620090 |
CAS-No. | 1303-86-2 | REACH Candidate List Substance | 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol |
RoHS Compliance Status | Compliant,With Exemption | RoHS Exemption | 6(c) |
SCIP notification number (Austria) | b72ae42b-6d26-42c7-bbff-c71c15bcf27c | SCIP notification number (Belgium) | 7e8d85b0-dec6-4d47-8a1d-b4a890d14264 |
SCIP notification number (Bulgaria) | ca7cf964-5a30-4608-adbc-f4870b7b7cd0 | SCIP notification number (Czech Republic) | fc6bb315-da69-4841-931e-d5e541f98ead |
SCIP notification number (Denmark) | 1081514b-8d27-433d-9b77-039036d02acd | SCIP notification number (Finland) | df2d9e9e-9e3f-4e37-913b-de80b3b8b08c |
SCIP notification number (France) | 9dc24a20-f78a-466b-9d7d-2a9753c511b3 | SCIP notification number (Germany) | cb8f348d-9c8c-443d-b168-c0c698e05ffb |
SCIP notification number (Hungary) | d8c1ecbf-42b6-48e2-8e71-7278dc922e60 | SCIP notification number (Italy) | 0c93aa3b-d946-4f68-a69a-33dad2dfe3f0 |
SCIP notification number (Netherlands) | f1122e45-401e-423b-90a3-41dc871b2757 | SCIP notification number (Poland) | f11c1f18-8098-4419-b3a1-0263f800e0b5 |
SCIP notification number (Romania) | 5da268e2-f35a-4cbc-88be-71d4cd060d5a | SCIP notification number (Sweden) | 74758c2a-a6f8-493d-93c1-9a89aabd2180 |
Specifications may be subject to change without notice