Product Model
750-474/005-000

Selling Points
- 1High Accuracy: Achieve precise measurements with a measuring error of < ±0.2% of the full scale value.
- 2Flexible Configuration: Easily configure via WAGO-I/O-CHECK or GSD for various industrial settings.
- 3Robust Connectivity: Utilize CAGE CLAMP® connections for secure and reliable wiring.
- 4Wide Operating Range: Operate in an extended temperature range of -20 °C to +60 °C.
- 5Durable Design: Built with a compact housing design and durable materials for long-lasting performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Number of analog inputs | 2 | Number of Channels | 2 |
Signal type | Current | Signal type (current) | 4 … 20?mADC |
Sensor connection | 2 x (2-wire,?3-wire) | Input filter frequency (analog) | 60Hz |
Input voltage (max.) | 24 V | Input voltage (note) | Non-linear, overload protected U = 1.2 V + 160 Ω x I meas |
Signal characteristics | Single-ended | Resolution [bit] | 15bits |
Input resistance (max.) | 220Ω | Data width | 2 x 16-bit data; 2 x 8-bit control/status (optional) |
Overvoltage protection | 30 V, reverse polarity protected | Noise rejection at sampling frequency | -100dB |
Noise rejection above sampling frequency | -40dB | Conversion time (typ. ≤) | 80ms |
Measurement error, reference temperature | 25°C | Measurement error, deviation max (upper-range value) ≤± | 0.1% |
Temperature error max. (upper-range value) ≤± | 0.01%/K | Supply voltage (system) | 5?VDC;?via data contacts |
Current consumption (5 V system supply) | 75mA | Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact) |
Isolation | 500?V system/field | Indicators | LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2 |
Number of incoming power jumper contacts | 2 | Number of outgoing power jumper contacts | 2 |
Connection technology: inputs / outputs | 8 x CAGE CLAMP? | Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5?mm2?/ 28 … 14?AWG | Fine-stranded conductor | 0.08 … 2.5?mm2?/ 28 … 14?AWG |
Strip length | 8 … 9?mm?/ 0.31 … 0.35?inches | Width | 12?mm?/ 0.472?inches |
Height | 100?mm?/ 3.937?inches | Depth | 69.8?mm?/ 2.748?inches |
Depth from upper-edge of DIN-rail | 62.6?mm?/ 2.465?inches | Mounting type | DIN-35 rail |
Color | light gray | Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 1.014MJ | Weight | 52.6g |
Conformity marking | CE | Ambient temperature (operation) | 0 … +55 °C |
Ambient temperature (storage) | -40 … +85 °C | Protection type | IP20 |
Pollution degree | 2 per IEC 61131-2 | Operating altitude | 0 … 2000?m / 0 … 6562 ft |
Mounting position | Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom | Relative humidity (without condensation) | 95% |
Vibration resistance | 4g per IEC 60068-2-6 | Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications | EMC emission of interference | per EN 61000-6-4, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 | Permissible pollutant concentration H<sub>2</sub>S at a relative humidity < 75% | 10ppm |
Permissible pollutant concentration SO <sub> 2 </sub> at a relative humidity < 75% | 25ppm | Product Group | 15 (I/O System) |
eCl@ss 10.0 | 27-24-26-01 | eCl@ss 9.0 | 27-24-26-01 |
ETIM 9.0 | EC001596 | ETIM 8.0 | EC001596 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 1?pcs |
Packaging type | box | Country of origin | DE |
GTIN | 4045454393328 | Customs tariff number | 8538901000 |
CAS-No. | 1303-86-2 | REACH Candidate List Substance | 4-Methyl-1,2-cyclohexanedicarboxylic anhydride |
RoHS Compliance Status | Compliant,With Exemption | RoHS Exemption | 6(c) |
SCIP notification number (Austria) | ebefc3ae-5a7a-45e1-a52f-8b1e8d613411 | SCIP notification number (Belgium) | ac62d792-722f-4c15-a67f-73009cfe5276 |
SCIP notification number (Bulgaria) | 6d47ba56-efeb-4553-b05c-71692429540c | SCIP notification number (Czech Republic) | 5442f626-3045-4cbb-abd2-cef86c93729f |
SCIP notification number (Denmark) | 2378bedb-8c60-4275-b37c-66909fc1c3f0 | SCIP notification number (Finland) | 7eb4830c-10be-42e6-b9fa-e1480a7584de |
SCIP notification number (France) | 9530970c-3d21-4243-8398-4717973621dd | SCIP notification number (Germany) | 53c5b5b5-a1c2-4ecc-af28-7699a53b3aa6 |
SCIP notification number (Hungary) | aacc3980-ff76-4a68-bbba-ed2b364b43b8 | SCIP notification number (Italy) | 732284de-b78a-454f-aafb-7f2aff4f8b03 |
SCIP notification number (Netherlands) | 4deb5dc0-9d22-4eb8-9402-16454713e9bf | SCIP notification number (Poland) | 71d3bbf3-cdf0-4515-9273-9cc680bf9e5f |
SCIP notification number (Romania) | a4ffb8a3-1aaf-436f-88cb-f8e0033e9269 | SCIP notification number (Sweden) | 991e72e4-6153-4b86-b343-ab428b52e946 |
Specifications may be subject to change without notice