Product Model
750-606

Selling Points
- 1Intrinsically Safe Design: Meets ATEX Ex and IECEx standards for safe operation in hazardous environments.
- 2Diagnostics and Monitoring: Includes LED indicators for input and output voltage status, ensuring continuous monitoring.
- 3Compact and Reliable: Measures 48x100x70.9mm, with a weight of 167.5g, making it ideal for DIN rail mounting.
- 4High Performance: Provides 24VDC with a maximum current of 1A, suitable for various industrial automation needs.
- 5Comprehensive Protection: Features electronic monitoring with automatic shutdown in case of short circuits or overloads.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Note | General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals! | Input voltage (note) | 24 VDC (?25 % … +30 %) |
Diagnostics | Input voltage failure, fuse triggered | Fuse | electronic |
Power consumption P<sub>max.</sub> | 29 W | Data width | 2 bits (input voltage failure, fuse triggered) |
Intrinsically safe Ex i | yes | Supply voltage (system) | 5?VDC;?via data contacts |
Current consumption (5 V system supply) | 7.5mA | Supply voltage (field) | 24 VDC (-25 … +30 %); (Adjacent Ex i modules are supplied with Uo= max. 27.3 V); via power jumper contacts (power supply via CAGE CLAMP?connection; transmission via spring contact) |
Supply voltage | 24?VDC;?(-25 % … +30 %); input voltage | Power loss P<sub>l</sub> | < 5 W |
Indicators | LED (A) green: operating voltage status: input; LED (B) green/red: operating voltage status: output | Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 1A | Identification | ATEXII 3 (1) G Ex ec [ia Ga] IIC T4 GcII (1) D [Ex ia Da] IIICI (M1) [Ex ia Ma] I |
Ex standard | EN IEC 60079-0, -7, -11 | Power supply (output) | Uo= 26.8 V (safe voltage per IEC 60079-11, protection level ia); Un= 24 V ± 0.3 V, In= 1 A |
Power supply (input) | Un= 24 VDC (-25 … +30 %); Pmax.= 29 W; Um= 253 V | Connection technology: field supply | 2 x CAGE CLAMP? |
Connection type 1 | Field supply | Solid conductor | 0.08 … 1.5?mm2?/ 28 … 14?AWG |
Fine-stranded conductor | 0.08 … 1.5?mm2?/ 28 … 14?AWG | Strip length | 5 … 6?mm?/ 0.2 … 0.24?inches |
Width | 48?mm?/ 1.89?inches | Height | 100?mm?/ 3.937?inches |
Depth | 70.9?mm?/ 2.791?inches | Depth from upper-edge of DIN-rail | 63.7?mm?/ 2.508?inches |
Mounting type | DIN-35 rail | Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 2.599MJ | Weight | 167.5g |
Conformity marking | CE | Ambient temperature (operation) | 0 … +55 °C |
Ambient temperature (storage) | -25 … +85 °C | Protection type | IP20 |
Pollution degree | 2 per IEC 61131-2 | Operating altitude | 0 … 2000?m / 0 … 6562 ft |
Mounting position | Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom | Relative humidity (without condensation) | 95% |
Vibration resistance | 4g per IEC 60068-2-6 | Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications | EMC emission of interference | per EN 61000-6-3, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 | Permissible pollutant concentration H<sub>2</sub>S at a relative humidity < 75% | 10ppm |
Permissible pollutant concentration SO <sub> 2 </sub> at a relative humidity < 75% | 25ppm | Product Group | 15 (I/O System) |
eCl@ss 10.0 | 27-24-26-10 | eCl@ss 9.0 | 27-24-26-10 |
ETIM 9.0 | EC001600 | ETIM 8.0 | EC001600 |
PU (SPU) | 1?pcs | Packaging type | box |
Country of origin | DE | GTIN | 4045454961909 |
Customs tariff number | 8538901000 | RoHS Compliance Status | Compliant,No Exemption |
SCIP notification number (Austria) | c0e961b9-f5ee-4b65-a1a8-472aee7a2b4c | SCIP notification number (Belgium) | 9a9fbad1-2151-4ca2-aec5-25ab8f123037 |
SCIP notification number (Bulgaria) | ed072b21-fb78-4134-9934-dfa4a6dc0ef4 | SCIP notification number (Czech Republic) | 266c66db-8acb-4f00-bf69-094ee6553caa |
SCIP notification number (Denmark) | 350710b9-e9a4-4603-aaf5-169b93ff0e77 | SCIP notification number (Finland) | 8ff26ff3-9f09-4bb8-aedc-18be5f80fba7 |
SCIP notification number (France) | 8535d1d5-e475-4e2e-a292-5ec098a62a8b | SCIP notification number (Germany) | 8624e861-a34f-472f-901f-a8b55966be77 |
SCIP notification number (Hungary) | a933bfdc-ce3e-40d2-95cd-93c13d3796c4 | SCIP notification number (Italy) | f9a05418-8ba1-4d38-9d5d-9faba4db04de |
SCIP notification number (Netherlands) | 9e17eb72-481a-4d00-bf13-7abd58508e22 | SCIP notification number (Poland) | 25b955c9-d2f8-4744-b703-a5b0acbd030b |
SCIP notification number (Romania) | 737c4cd0-1a61-4064-827d-49007a2f8b50 | SCIP notification number (Sweden) | a8f2598e-8225-4e57-84ed-8ccaa13ba2aa |
Order text | Power Supply; 24 VDC; Diagnostics | ECCN | NO US CLASSIFICATION |
Specifications may be subject to change without notice