Product Model
750-610/040-000

Selling Points
- 1High-performance industrial automation component
- 2Precision control for complex systems
- 3Reliable operation in demanding environments
- 4Compact design for space-efficient installations
- 5Compatible with a wide range of industrial protocols
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Signal type | Voltage | Signal type (voltage) | 24?VDC |
Diagnostics | Supply voltage (field): Detection “on” at > 15 VDC; Detection “off” at < 5 VDC | Fuse | 5 x 20; T 6.3 A (not included) |
Data width | 2 bits (1 bit current monitoring, 1 bit fuse fault) | Supply voltage (system) | 5?VDC;?via data contacts |
Current consumption (5 V system supply) | 5mA | Supply voltage (field) | 24?VDC?(-25 … +30?%);?via power jumper contacts (power supply via CAGE CLAMP?connection; transmission via spring contact); Derating must be observed! |
Rated surge voltage | 1?kV | Indicators | LED (A) red: defective fuse error; LED (B) green: power supply status |
Number of outgoing power jumper contacts | 2 | Current carrying capacity (power jumper contacts) | 6.3A |
Derating | Derating (supply voltage):Ambient temperatures under laboratory conditions: (?25 … +30°%);for ?40 … +55°°C: 24°V (?25 … +20°%);for +55 … +70°°C: 24°V (?25 … +10°%);Lower limit in all temperature ranges: ?27.5°% (including 15°% residual ripple) | Connection technology: field supply | 6 x CAGE CLAMP? |
Connection type 1 | Field supply | Solid conductor | 0.25 … 2.5?mm2?/ 24 … 14?AWG |
Fine-stranded conductor | 0.25 … 2.5?mm2?/ 24 … 14?AWG | Strip length | 8 … 9?mm?/ 0.31 … 0.35?inches |
Width | 12?mm?/ 0.472?inches | Height | 100?mm?/ 3.937?inches |
Depth | 67.8?mm?/ 2.669?inches | Depth from upper-edge of DIN-rail | 60.6?mm?/ 2.386?inches |
Mounting type | DIN-35 rail | Color | dark gray |
Housing material | Polycarbonate; polyamide 6.6 | Fire load | 0.995MJ |
Weight | 46.8g | Conformity marking | CE |
Ambient temperature (operation) | -40 … +70 °C | Ambient temperature (storage) | -40 … +85 °C |
Protection type | IP20 | Pollution degree | 2 per IEC 61131-2 |
Operating altitude | Without temperature derating: 0 … 2000?m; with temperature derating: 2000 … 5000?m (0.5?K/100?m); 5000?m (max.) | Mounting position | Horizontal left, horizontal up, vertical top and vertical bottom |
Relative humidity (without condensation) | 95% | Relative humidity (with condensation) | Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation) |
Vibration resistance | Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373 | Shock resistance | Per IEC 60068-2-27 (15g/11?ms/half-sine/1,000 shocks; 25g/6?ms/1,000 shocks), EN 50155, EN 61373 |
EMC immunity to interference | per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26;EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994 | EMC emission of interference | Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 | Permissible pollutant concentration H<sub>2</sub>S at a relative humidity < 75% | 10ppm |
Permissible pollutant concentration SO <sub> 2 </sub> at a relative humidity < 75% | 25ppm | eCl@ss 10.0 | 27-24-26-10 |
eCl@ss 9.0 | 27-24-26-10 | ETIM 9.0 | EC001600 |
ETIM 8.0 | EC001600 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 1?pcs | Packaging type | box |
Country of origin | DE | GTIN | 4055143673280 |
Customs tariff number | 8538901000 | CAS-No. | 1303-86-2 |
REACH Candidate List Substance | 4-Methyl-1,2-cyclohexanedicarboxylic anhydride | RoHS Compliance Status | Compliant,With Exemption |
RoHS Exemption | 6(c) | SCIP notification number (Austria) | 5f0c7827-9056-4403-919f-420f429d751a |
SCIP notification number (Belgium) | 2edf10d9-8c12-40bd-8011-fbe8ce49e361 | SCIP notification number (Bulgaria) | b82956fd-85bb-4cbd-a2cc-a9bc592990fb |
SCIP notification number (Czech Republic) | 82e5795b-c668-4146-a53d-177d0259cf41 | SCIP notification number (Denmark) | 1bd7535d-e265-4ac1-8c16-186931171d10 |
SCIP notification number (Finland) | 5962422f-3c57-4f7b-a3da-35baa82af7e2 | SCIP notification number (France) | c92d10ad-087d-467a-ae18-ca1c710aca9e |
SCIP notification number (Germany) | 3de830d2-f834-46cd-a92d-07cedb6f6e1d | SCIP notification number (Hungary) | 611a453b-d55d-4750-aa79-35dfce68ebf1 |
SCIP notification number (Italy) | 8828d7af-0d50-4f3c-a4fa-39016dc28d64 | SCIP notification number (Netherlands) | b4dba505-328b-43e3-9de9-7a6a8b8b5bde |
SCIP notification number (Poland) | c5160df5-3cf1-4e08-9c03-053c8db0dc6a | SCIP notification number (Romania) | d5034573-5033-4249-912c-3118e0e384f6 |
SCIP notification number (Sweden) | 26fa49de-0c39-463d-a1fd-2cba44a071c1 |