wago 750-8204

Selling Points

  • 1Dual Ethernet Interfaces: Enable line topology wiring with integrated switches for seamless network connectivity.
  • 2Versatile Communication: Supports RS-232, RS-485, CAN, and CANopen protocols for diverse industrial applications.
  • 3Compact Design: Measuring 112 mm x 71.9 mm x 100 mm, perfect for space-constrained environments.
  • 4Webserver Integration: Provides user configuration options and real-time status updates via an integrated webserver.
  • 5Robust Construction: Built with polycarbonate and polyamide 6.6, ensuring durability in harsh industrial conditions.
Product Details
750-8204
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Communications
CANopen
ETHERNET protocols
DHCP
Visualization
Web-Visu
Operating system
Real-time Linux (with PREEMPT_RT patch)
CPU
Cortex A8; 600 MHz
Programming languages per IEC 61131-3
Instruction List (IL)
Programming environment
e!COCKPIT(based on CODESYS V3)
Configuration options
e!COCKPIT
Transmission rate
ETHERNET:?10/100?Mbit/s
Transmission medium (communication/fieldbus)
ETHERNET:?Twisted Pair S-UTP; 100?Ω; Cat.?5; 100?m maximum cable length
Main memory (RAM)
256MB
Internal memory (flash)
256MB
Non-volatile hardware memory
128Kbytes
Program memory
CODESYS V2:?16?MB;?CODESYS V3:?60?MB (Program and data memory (dynamically distributed))
Data memory
CODESYS V2:?64?MB;?CODESYS V3:?60?MB?Program and data memory (dynamically distributed)
Non-volatile software memory
128.Kbytes
Type of memory card
SD and SDHC up to 32 GB (all guaranteed properties only valid with WAGO's memory card)
Memory card slot
Push-push mechanism; Cover lid (sealable)
Number of modules per node (max.)
250
Number of modules without a bus extension (max.)
64
Input and output process image (internal) max.
1000?words/1000?words
Input and output process image (Modbus?) max.
CODESYS V2: 1000?words/1000?words
Input and output process image (CAN) max.
2000?words/2000?words
Indicators
LED (SYS, RUN, I/O, CAN, U1 … U6) red/green/orange: Status system, program, internal data bus, CANopen, status programmable by user (can be used via CODESYS library); LED (A, B) green: Status system power supply, field supply
Supply voltage (system)
24?VDC (-25 … +30?%);?via pluggable connector (CAGE CLAMP?connection)
Input current (typ.) at nominal load (24?V)
550mA
Total current (system supply)
1,700mA
Supply voltage (field)
24?VDC?(-25 … +30?%);?via power jumper contacts
Current carrying capacity (power jumper contacts)
10A
Number of outgoing power jumper contacts
3
Isolation
500?V system/field
Connection technology: communication/fieldbus
CANopen:?1 x D-sub 9 plug;?Modbus (TCP, UDP):?2 x RJ-45;?Modbus RTU:?1 x D-sub 9 socket;?RS-232 serial interface:?1 x D-sub 9 socket;?RS-485 interface:?1 x D-sub 9 socket
Connection technology: system supply
2 x CAGE CLAMP?
Connection technology: field supply
6 x CAGE CLAMP?
Connection type 1
System/field supply
Solid conductor
0.08 … 2.5?mm2?/ 28 … 14?AWG
Fine-stranded conductor
0.08 … 2.5?mm2?/ 28 … 14?AWG
Strip length
8 … 9?mm?/ 0.31 … 0.35?inches
Connection technology: device configuration
1 x Male connector; 4-pole
Width
112?mm?/ 4.409?inches
Height
71.9?mm?/ 2.831?inches
Depth
100?mm?/ 3.937?inches
Weight
246.7g
Color
light gray
Housing material
Polycarbonate; polyamide 6.6
Conformity marking
CE
Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-40 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
without temperature derating: 0 … 2000?m; with temperature derating: 2000 … 5000?m (0.5?K/100?m); 5000?m (max.)
Relative humidity (without condensation)
95%
Mounting position
Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Mounting type
DIN-35 rail
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
per EN 61000-6-2, marine applications
EMC emission of interference
per EN 61000-6-3, marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Fire load
2.883MJ
Permissible pollutant concentration H<sub>2</sub>S at a relative humidity &#60; 75%
10ppm
Permissible pollutant concentration SO <sub> 2 </sub> at a relative humidity &#60; 75%
25ppm
Product Group
15 (I/O System)
eCl@ss 10.0
27-24-26-07
eCl@ss 9.0
27-24-26-07
ETIM 9.0
EC000236
ETIM 8.0
EC000236
ECCN
NO US CLASSIFICATION
PU (SPU)
1?pcs
Packaging type
box
Country of origin
DE
GTIN
4050821739487
Customs tariff number
8537109160
End of Sale
2020-12-31
End of Production
2021-01-05
End of Delivery
2021-01-15
End of Service and Repair
2022-12-31
CAS-No.
12060-00-3
REACH Candidate List Substance
2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
6(c)
SCIP notification number (Austria)
74b32d0a-7550-4e03-b98d-052eb3b07115
SCIP notification number (Belgium)
92149efd-f6be-426f-aa5a-86284c65b68b
SCIP notification number (Bulgaria)
064ca148-7e86-4348-9bcf-1c4d4c6edb56
SCIP notification number (Czech Republic)
8cc1aad5-6a51-4557-94c6-bc98320bb26e
SCIP notification number (Denmark)
6d49d2fe-4429-4359-8a31-404a67920ab4
SCIP notification number (Finland)
0875e752-56c3-4a55-b6b5-3b10addd0568
SCIP notification number (France)
a0d27508-ee80-45a3-85a5-e0c9ad953f81
SCIP notification number (Germany)
3a586e71-db92-4d3c-9b3a-d63fef15e540
SCIP notification number (Hungary)
b35099c1-1e24-48e1-bdca-cae026f17404
SCIP notification number (Italy)
1ccf2f2a-1057-4a6e-baa9-53abaa2b4b43
SCIP notification number (Netherlands)
f51b8938-bd06-4eae-826a-66256e2bc037
SCIP notification number (Poland)
fd87595f-e936-4e34-ae51-7467e8f64fba
SCIP notification number (Romania)
0eeb9881-7156-46dd-afd5-b3d246834c47
SCIP notification number (Sweden)
abba07cf-157d-4cc6-a75f-098b50e6cf31

Specifications may be subject to change without notice