Product Model

750-8206/040-001

In Stock
Last updated: 2025/4/18
wago 750-8206/040-001

Selling Points

  • 1Supports multiple communication protocols including PROFIBUS, CANopen, Modbus (TCP, UDP), Ethernet, and RS-232/485.
  • 2Ideal for operation in extreme environments with extended temperature range, high immunity to impulse voltages and electromagnetic interference.
  • 3Maintenance-free design with configuration via CODESYS or Web-Based Management interface.
  • 4Features 2 x Ethernet ports for enhanced connectivity and data transfer.
  • 5Compliant with various telecontrol protocols and IEC standards for robust operation.
Product Details
750-8206/040-001
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Communications
PROFIBUS
ETHERNET protocols
DHCP
Telecontrol protocols
IEC 60870-5-101/-103/-104
Visualization
Web-Visu
Operating system
Real-time Linux (with PREEMPT_RT patch)
CPU
Cortex A8; 600 MHz
Programming languages per IEC 61131-3
Instruction List (IL)
Programming environment
e!COCKPIT(based on CODESYS V3)
Configuration options
e!COCKPIT
Transmission rate
ETHERNET:?10/100?Mbit/s
Transmission medium (communication/fieldbus)
ETHERNET:?Twisted Pair S-UTP; 100?Ω; Cat.?5; 100?m maximum cable length
Main memory (RAM)
256MB
Internal memory (flash)
256MB
Non-volatile hardware memory
128Kbytes
Program memory
CODESYS V2:?16?MB;?CODESYS V3:?60?MB (Program and data memory (dynamically distributed))
Data memory
CODESYS V2:?64?MB;?CODESYS V3:?60?MB?Program and data memory (dynamically distributed)
Non-volatile software memory
128.Kbytes
Type of memory card
SD card
Memory card slot
Push-push mechanism; Cover lid (sealable)
Number of modules per node (max.)
64
Input and output process image (internal) max.
1000?words/1000?words
Input and output process image (Modbus?) max.
CODESYS V2: 1000?words/1000?words; CODESYS V3: 32000?words/32000?words
Input and output process image (PROFIBUS) max.
244?bytes/244?bytes
Input and output process image (CAN) max.
2000?words/2000?words
Indicators
LED (SYS, RUN, I/O, CAN, BF, DIA, U1 … U4) red/green/orange: Status system, program, internal data bus, CANopen, PROFIBUS, PROFIBUS diagnostics, status programmable by user (can be used via CODESYS library); LED (A, B) green: System power supply status, field supply
Derating
Derating (supply voltage):Ambient temperatures under laboratory conditions: (?25 … +30°%);for ?40 … +55°°C: 24°V (?25 … +20°%);for +55 … +70°°C: 24°V (?25 … +10°%);Lower limit in all temperature ranges: ?27.5°% (including 15°% residual ripple)
Supply voltage (system)
24?VDC;?via pluggable connector (CAGE CLAMP? connection); Derating must be observed!
Input current (typ.) at nominal load (24?V)
550mA
Power supply efficiency (typ.) at nominal load (24 V)
90%
Current consumption (5 V system supply)
600mA
Total current (system supply)
1,700mA
Supply voltage (field)
24?VDC;?Power supply via pluggable connector (CAGE CLAMP? connection); Transmission via power jumper contacts; Derating must be observed!
Current carrying capacity (power jumper contacts)
10A
Number of outgoing power jumper contacts
2
Ratings per
IEC/EN 60664-1
Rated surge voltage
1?kV
Connection technology: communication/fieldbus
PROFIBUS:?1 x D-sub 9 socket;?CANopen:?1 x D-sub 9 plug;?Modbus (TCP, UDP):?2 x RJ-45;?Modbus RTU:?1 x D-sub 9 socket;?RS-232 serial interface:?1 x D-sub 9 socket;?RS-485 interface:?1 x D-sub 9 socket;?Telecontrol protocol IEC 60870-5-101/-103:?1 x D-sub 9 socket;?Telecontrol protocol IEC 60870-5-104:?1 x RJ-45;?Telecontrol protocol IEC 61850:?1 x RJ-45;?Telecontrol protocol DNP3:?1 x RJ-45 or D-sub 9 socket
Connection technology: system supply
2 x CAGE CLAMP?
Connection technology: field supply
4 x CAGE CLAMP?
Connection type 1
System/field supply
Solid conductor
0.25 … 2.5?mm2?/ 24 … 14?AWG
Fine-stranded conductor
0.25 … 2.5?mm2?/ 24 … 14?AWG
Strip length
8 … 9?mm?/ 0.31 … 0.35?inches
Connection technology: device configuration
1 x Male connector; 4-pole
Width
112?mm?/ 4.409?inches
Height
100?mm?/ 3.937?inches
Depth
71.9?mm?/ 2.831?inches
Depth from upper-edge of DIN-rail
64.7?mm?/ 2.547?inches
Weight
262g
Color
dark gray
Housing material
Polycarbonate; polyamide 6.6
Conformity marking
CE
Ambient temperature (operation)
-40 … +70 °C
Ambient temperature (storage)
-40 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
without temperature derating: 0 … 2000?m; with temperature derating: 2000 … 5000?m (0.5?K/100?m); 5000?m (max.)
Relative humidity (without condensation)
95%
Relative humidity (with condensation)
Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Mounting position
Horizontal left, horizontal up, vertical top and vertical bottom
Mounting type
DIN-35 rail
Vibration resistance
per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
Shock resistance
per IEC 60068-2-27 (15g/11?ms/half-sine/1,000 shocks; 25g/6?ms/1,000 shocks), EN 50155, EN 61373
EMC immunity to interference
per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26;EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
EMC emission of interference
per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Fire load
3.275MJ
Permissible pollutant concentration H<sub>2</sub>S at a relative humidity &#60; 75%
10ppm
Permissible pollutant concentration SO <sub> 2 </sub> at a relative humidity &#60; 75%
25ppm
eCl@ss 10.0
27-24-26-07
eCl@ss 9.0
27-24-26-07
ETIM 9.0
EC000236
ETIM 8.0
EC000236
ECCN
NO US CLASSIFICATION
PU (SPU)
1?pcs
Packaging type
box
Country of origin
DE
GTIN
4055143353601
Customs tariff number
8537109160
End of Sale
2023-01-13
End of Production
2023-01-16
End of Delivery
2023-02-28
End of Service and Repair
2025-02-28
CAS-No.
1303-86-2
REACH Candidate List Substance
2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
6(c)
SCIP notification number (Austria)
156d1ced-2ab0-4c26-9cbd-93192d73982e
SCIP notification number (Belgium)
025c8bbc-2a8a-44d3-9b8b-0c26b982a694
SCIP notification number (Bulgaria)
d551665b-6cf4-4adb-87bb-1e1d5a6484ff
SCIP notification number (Czech Republic)
65f52ef3-755b-4a2d-b249-ac058ad30e18
SCIP notification number (Denmark)
0f781a92-b226-434a-8813-8877baf36bcb
SCIP notification number (Finland)
9819fc64-b234-498f-9d5f-183465d5c2b1
SCIP notification number (France)
3bf3368e-7170-4dfc-ab33-947b39adaaed
SCIP notification number (Germany)
8c752272-fe3b-40e6-9e58-538f14fda1da
SCIP notification number (Hungary)
8acaafbf-d037-4302-bc52-1bf4128b0591
SCIP notification number (Italy)
e82bd53d-741a-4dd3-91ae-5d69b3b49422
SCIP notification number (Netherlands)
2b38f48b-80b4-49d7-884a-3162e545a091
SCIP notification number (Poland)
c8cecd17-e9fa-43a7-bea1-2ae3f3d1fc50
SCIP notification number (Romania)
da5bf30f-b18b-4917-8b18-ab0ea87c4e14
SCIP notification number (Sweden)
3c8be863-4bf1-403f-b738-46c780666d30

Specifications may be subject to change without notice