  • 1High-Speed Communication: Supports BACnet/IP at 10/100 Mbit/s and serial interface at 9.6 kBd and 115.2 kBd.
  • 2Versatile Connectivity: Equipped with RJ-45 for BACnet/IP, Modbus TCP/UDP, and RS-232 serial interface.
  • 3Advanced Configuration: Includes WAGO-I/O-CHECK and BACnet Configurator for easy setup.
  • 4Comprehensive Programming: Supports IEC 61131-3 programming languages like IL, LD, FBD, CFC, ST, and SFC.
  • 5Reliable Performance: Operates within a temperature range of 0 to +55°C and has a shock resistance of 15g.
Product Details
750-830
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Note
The WAGO BACnet Configurator can be downloaded for free at www.wago.com.
Communications
BACnet/IP
ETHERNET protocols
HTTP
Visualization
Web-Visu
Programming languages per IEC 61131-3
Instruction List (IL)
Programming environment
WAGO-I/O-PROV2.3 (based on CODESYS V2.3)
Configuration options
WAGO-I/O-CHECK
Network length (max.)
limited by IEEE 802.3 specification
Transmission rate
BACnet/IP: 10/100 Mbit/s; Serial interface: 9.6/115.2 kBd
Bus segment length (max.)
BACnet/IP: 100?m;?Serial interface: 15?m
Transmission medium (communication/fieldbus)
BACnet/IP:?S-UTP; 100 Ω; Cat. 5;?Serial interface:?Shielded Cu cable 2 (4) x 0.25 mm2
Internal memory (flash)
4.5MB
Program memory
512?KB
Data memory
256?KB
Non-volatile software memory
24Kbytes
Memory for fieldbus input variables (max.)
512Byte
Memory for fieldbus output variables (max.)
512Byte
Number of modules per node (max.)
250
Number of modules without a bus extension (max.)
64
Input and output process image (fieldbus) max.
1953.125?bytes/1953.125?bytes
Device-specific
BACnet device profile: B-BC (BACnet building controller); BACnet revision: 1.7; BACnet implementation per EN ISO 16484-5 =ANSI/ASHRAE 135-2004
Indicators
LED (LINK/ACT) green: Network connection; LED (BT, MS, NS) red/green: Status of BACnet, node, network; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply
Supply voltage (system)
24?VDC (-25 … +30?%);?via pluggable connector (CAGE CLAMP?connection)
Input current (typ.) at nominal load (24?V)
500mA
Power supply efficiency (typ.) at nominal load (24 V)
87%
Current consumption (5 V system supply)
300mA
Total current (system supply)
1,700mA
Supply voltage (field)
24?VDC?(-25 … +30?%);?via power jumper contacts
Current carrying capacity (power jumper contacts)
10A
Number of outgoing power jumper contacts
3
Isolation
500?V system/field
WSPCert certification
ISO 16484-5:2010
Connection technology: communication/fieldbus
BACnet/IP:?1 x RJ-45;?Modbus (TCP, UDP):?1 x RJ-45;?RS-232 serial interface:?1 x D-sub 9 socket
Connection technology: system supply
2 x CAGE CLAMP?
Connection technology: field supply
6 x CAGE CLAMP?
Connection type 1
System/field supply
Solid conductor
0.08 … 2.5?mm2?/ 28 … 14?AWG
Fine-stranded conductor
0.08 … 2.5?mm2?/ 28 … 14?AWG
Strip length
8 … 9?mm?/ 0.31 … 0.35?inches
Connection technology: device configuration
1 x Male connector; 4-pole
Width
50.5?mm?/ 1.988?inches
Height
71.1?mm?/ 2.799?inches
Depth
100?mm?/ 3.937?inches
Weight
192.4g
Color
light gray
Housing material
Polycarbonate; polyamide 6.6
Conformity marking
CE
Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-25 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
without temperature derating: 0 … 2000?m; with temperature derating: 2000 … 5000?m (0.5?K/100?m); 5000?m (max.)
Relative humidity (without condensation)
95%
Mounting position
Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Mounting type
DIN-35 rail
Vibration resistance
per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
per EN 61000-6-2, marine applications
EMC emission of interference
per EN 61000-6-3, marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Fire load
3.935MJ
Permissible pollutant concentration H<sub>2</sub>S at a relative humidity &#60; 75%
10ppm
Permissible pollutant concentration SO <sub> 2 </sub> at a relative humidity &#60; 75%
25ppm
Product Group
15 (I/O System)
eCl@ss 10.0
27-24-26-07
eCl@ss 9.0
27-24-26-07
ECCN
NO US CLASSIFICATION
PU (SPU)
1?pcs
Packaging type
box
Country of origin
DE
GTIN
4045454636401
Customs tariff number
8537109160
End of Sale
2019-06-30
End of Production
2019-07-05
End of Delivery
2019-07-15
End of Service and Repair
2021-06-29
CAS-No.
12060-00-3
REACH Candidate List Substance
2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
6(c)
SCIP notification number (Austria)
dd8331d2-a516-42f3-b10b-adac42811586
SCIP notification number (Belgium)
35f6e720-fbb2-43fa-b766-e7880497cb65
SCIP notification number (Bulgaria)
694d7bd5-6d04-47e9-8b56-1cf10d634acb
SCIP notification number (Czech Republic)
d85c0b64-8196-4fb0-961f-d6fd810f9907
SCIP notification number (Denmark)
2a29206b-8183-4211-b7f0-40d092ceb40f
SCIP notification number (Finland)
e11d0668-bcef-4ba0-b2c9-eb11897b6f23
SCIP notification number (France)
76b69654-80b0-4f17-bb6f-dc2f33f7f00e
SCIP notification number (Germany)
4a09ba52-4d43-474d-9af6-2d35189c2e22
SCIP notification number (Hungary)
9e1718e6-382e-44df-b70e-a8dada131d2c
SCIP notification number (Italy)
a1aefffe-549c-4994-b659-14d27bc5a5a7
SCIP notification number (Netherlands)
a58ade70-5c7c-4b49-b696-7b744eb26b5c
SCIP notification number (Poland)
6c7ac4ee-ce30-4c94-aad3-edfb56347796
SCIP notification number (Romania)
7e67b2b8-de28-4d7b-83c6-6b5a93c9d025
SCIP notification number (Sweden)
f7fb0133-70f0-4dc1-9e49-a9ef3473181f

Specifications may be subject to change without notice