Product Model
753-469

Selling Points
- 1Accurately measure temperature with 2 thermocouple K inputs.
- 2Ensure reliable operation with a green LED indicating readiness and error-free communication.
- 3Conveniently integrate into your industrial setup with DIN rail mounting.
- 4Achieve 0.1°C resolution and 320ms conversion time for precise measurements.
- 5Meets marine application approvals (DNV-CG-0339) and industrial standards for harsh environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Note | Pluggable connectors and coding fingers (753 Series) are not included. | Number of analog inputs | 2 |
Number of Channels | 2 | Signal type | Thermocouple |
Sensor connection | 2 x (2-wire) | Data width | 2 x 16-bit data; 2 x 8-bit control/status (optional) |
Internal resistance | 1000kΩ | Resolution (over entire range) | 0.1?°C |
Conversion time (typ. ≤) | 320ms | Measurement error (25 °C) | < ±6 K (voltage input < ±2 K; cold junction compensation < ±4 K) |
Temperature coefficient | < ±0.2 K/K | Sensor types | Thermocouple K |
Temperature range | ?100 … +1370?°C | Cold junction compensation | at each pair of terminal blocks |
Supply voltage (system) | 5?VDC;?via data contacts | Current consumption (5 V system supply) | 65mA |
Isolation | 500?V system/field | Indicators | LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2 |
Connection technology: inputs / outputs | 8 x CAGE CLAMP? | Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5?mm2?/ 28 … 14?AWG | Fine-stranded conductor | 0.08 … 2.5?mm2?/ 28 … 14?AWG |
Strip length | 9 … 10?mm?/ 0.35 … 0.39?inches | Width | 12?mm?/ 0.472?inches |
Height | 100?mm?/ 3.937?inches | Depth | 69.8?mm?/ 2.748?inches |
Depth from upper-edge of DIN-rail | 62.6?mm?/ 2.465?inches | Mounting type | DIN-35 rail |
Pluggable connector | Pluggable | Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 | Fire load | 0.882MJ |
Weight | 56g | Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C | Ambient temperature (storage) | -40 … +85 °C |
Protection type | IP20 | Pollution degree | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000?m / 0 … 6562 ft | Mounting position | Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom |
Relative humidity (without condensation) | 95% | Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 | EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-4, marine applications | Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H<sub>2</sub>S at a relative humidity < 75% | 10ppm | Permissible pollutant concentration SO <sub> 2 </sub> at a relative humidity < 75% | 25ppm |
Product Group | 15 (I/O System) | eCl@ss 10.0 | 27-24-26-01 |
eCl@ss 9.0 | 27-24-26-01 | ETIM 9.0 | EC001596 |
ETIM 8.0 | EC001596 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 1?pcs | Packaging type | box |
Country of origin | DE | GTIN | 4045454394493 |
Customs tariff number | 8538901000 | CAS-No. | 1303-86-2 |
REACH Candidate List Substance | 4-Methyl-1,2-cyclohexanedicarboxylic anhydride | RoHS Compliance Status | Compliant,With Exemption |
RoHS Exemption | 6(c) | SCIP notification number (Austria) | 47f0972f-5ddb-43fd-88af-3c06eef123f2 |
SCIP notification number (Belgium) | 3b8470ad-3c70-4f8b-adb3-22379a5504e4 | SCIP notification number (Bulgaria) | 76e4824e-cb23-4f2f-adf0-3d0c7b83a4f7 |
SCIP notification number (Czech Republic) | b69f7d30-86fe-445c-ae77-d65dcf8416f7 | SCIP notification number (Denmark) | 1bd9dfa0-42fe-4f08-b716-3f0b4f3b3201 |
SCIP notification number (Finland) | 4f8760e6-a141-460d-9525-6878106a3195 | SCIP notification number (France) | 258d3c82-b64f-4e16-b73e-7e1db18422b5 |
SCIP notification number (Germany) | 273e1d5c-d668-4155-b4d0-a9d320c43155 | SCIP notification number (Hungary) | ab384b18-8330-4dac-8e12-24a67fe4b62a |
SCIP notification number (Italy) | afc9d2e8-bff3-494b-ba5f-deb355657079 | SCIP notification number (Netherlands) | 8fd69244-4f89-4351-9b5c-bf643cad89c8 |
SCIP notification number (Poland) | 0be8a598-003f-41a2-a20f-5b4c284bb5dc | SCIP notification number (Romania) | 48a25004-5aba-4a6f-8adb-4022119c3135 |
SCIP notification number (Sweden) | 8c33ca30-1720-4dbc-bde7-d2742ffaf370 |
Specifications may be subject to change without notice