Selling Points
- 1Ensures reduced environmental contamination and improved fire safety.
- 2Supports up to 16A, suitable for high-power applications.
- 3Built with polyamide insulation and tinned copper contacts for long-lasting performance.
- 4Provides secure and error-free connections with mechanical coding.
- 5Offers protection against mismating and environmental factors with an IP rating.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Note | Cables with a different fire class can be found in the eShop. | Total number of potentials | 5 |
PE function | Preceding PE contact | Conductor preparation | ultrasonically tip-bonded |
Pin spacing | 10 mm / 0.394 inches | Width | 47 mm / 1.85 inches |
Height | 15.38 mm / 0.606 inches | Total length | 6m |
Use | DALI, Lighting Management | Coding | I |
Variable coding | No | Marking | N ? L DA- DA+ |
Potential Marking | N ? L DA- DA+ | Mating force of a plug-in connection | approx. 20 … 70 N (depending on pole number) |
Retention force of a plug-in connection | when locked: > 80N | Unmating force of a plug-in connection | when unlocked: approx. 20 … 70 N (depending on pole number) |
Number of mating cycles | 200, without resistive load | Connection type | Plug - free end |
Type of pre-assembled cable | Connecting cable | Cable type | H05Z1Z1-F 5G1.5 |
Protection type | IP20; When mated: IP2xC (These compact connectors are not designed for use in open, easily accessible areas!) | Mismating protection | Yes |
Note on mismating protection | AllWINSTA?components are 100% protected against mismating when:a.) plugging different numbers of polesb.) plugging while rotated 180c.) plugging while laterally staggeredd.) plugging one pole | Locking lever | Can be retrofitted |
Locking of plug-in connection | Locking lever | Note on locking system | All connectors for mounted installations (snap-in versions for lighting fixtures or devices, all types of PCB and distribution connectors) are factory-equipped with locking levers to ensure plugs and sockets are securely locked. Additional locking levers are only required for flying leads (plug/socket). |
Note (material data) | Information on material specifications can be found here | Color | blue |
Insulation material (main housing) | Polyamide (PA66) | Flammability class per UL94 | V0 |
Fire class per EN 50575 | Dca | Contact material | Copper or copper alloy; surface-treated |
Contact plating | Tin | Fire load | 0.619MJ |
Connector color | blue | Strain relief color | white |
Printing color of strain relief | black | Sheathed cable color | white |
Printing color of sheathed cable | black | Halogen-free | Yes |
Silicon-free | Yes | Sheath material | Halogen-free |
Rubber cable | No | Weight | 978.3g |
Copper weight of the pipe | 0.072kg/m | Processing temperature | -5 … +40 °C |
Continuous operating temperature | -35 … +85 °C | Note on continuous operating temperature | Cable for temperatures ≤ 70 °C (including halogen-free)Insulating parts for temperatures ≤ 105 °C |
ETIM 9.0 | EC002587 | ETIM 8.0 | EC002587 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 1 pcs |
Packaging type | unpacked | Country of origin | DE |
GTIN | 4066966454949 | Customs tariff number | 85444290900 |
RoHS Compliance Status | Compliant,No Exemption | Ratings per | IEC/EN 60664-1 |
Rated voltage (III / 3) | 400V | Rated impulse voltage (III / 3) | 6kV |
Rated current | 16A | Legend (ratings) | (III / 3) ? Overvoltage category III / Pollution degree 3 |
Note on contact resistance | approx. 1 m? of contact resistanceapprox. 0.25 m? contact transition plug/socket | Strip length | 9 mm / 0.35 inches |
Number of poles | 5 | Wire cross-section | 1.5mm2 |
Strip length (outer insulation) | 55mm |
Specifications may be subject to change without notice