Product Model
787-1216

Selling Points
- 1Compact design for easy installation in distribution boards and control panels.
- 2Reliable 24VDC output voltage with 4.2A output current.
- 3Suitable for both parallel and series operation.
- 4Electrically isolated output voltage (SELV) per EN 60335-1 and UL 60950-1.
- 5High efficiency with typical efficiency of 90% at 230VAC.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Protection class | I | Protection type | IP20; per EN 60529 |
Pollution degree | 2 | Transient suppression (primary) | Varistor |
Overvoltage protection; secondary | ≤ 31 VDC (in the event of a fault) | Short-circuit-protected | Yes |
Open-circuit-proof | Yes | Parallel operation | Yes |
Series operation | Yes | MTBF | > 500,000 h (per IEC 61709) |
Connection type 1 | Input/Output | Connection technology | Push-in CAGE CLAMP? |
WAGO connector | picoMAX?5.0, WAGO 2092 Series | Solid conductor | 0.2 … 2.5?mm2?/ 24 … 12?AWG |
Fine-stranded conductor | 0.2 … 2.5?mm2?/ 24 … 12?AWG | Strip length | 9 … 10?mm?/ 0.35 … 0.39?inches |
Width | 108?mm?/ 4.252?inches | Height | 90?mm?/ 3.543?inches |
Depth | 56?mm?/ 2.205?inches | Depth from upper-edge of DIN-rail | 52.5?mm?/ 2.067?inches |
Note (dimensions) | Depth: 48 mm (without cover) | Housing design | DIN-rail-mount enclosure |
Mounting type | DIN-35 rail | Flammability class per UL94 | V0 |
Weight | 456.9g | Ambient temperature (operation) | -25 … +70 °C |
Ambient temperature (storage) | -40 … +85 °C | Relative humidity | 95% (no condensation permissible) |
Derating | ?2.66 %/K (> 55 °C) | Climatic category | 3K3 (per EN 60721; except for low air pressure) |
Conformity marking | CE | Standards/specifications | EN 61204-3 |
eCl@ss 10.0 | 27-04-07-01 | eCl@ss 9.0 | 27-04-07-01 |
ETIM 9.0 | EC002540 | ETIM 8.0 | EC002540 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 1?pcs |
Packaging type | box | Country of origin | CN |
GTIN | 4055143907804 | Customs tariff number | 8504409510 |
RoHS Compliance Status | Compliant,No Exemption | SCIP notification number (Bulgaria) | ca2e8647-4913-4ddb-9aae-499d1789bbbd |
SCIP notification number (Czech Republic) | eb73b17d-78c9-4111-8352-17210dfcbfc9 | Phases | 1 |
Nominal input voltage [V] | 1 x AC?100 … 240?V | Input voltage range | 1 x AC?85 … 264?V;?DC?125 … 375?V |
Input voltage derating | -2 %/V (< 100 VAC); -1.33 %/V (< 140 VDC) | Nominal mains frequency range | 47 … 63 Hz;0 Hz |
Input current I<sub>i</sub> | ≤?2.5?A | Inrush current | ≤?20?A |
Power factor | ≥?0.5 | Power factor correction (PFC) | Passive |
Mains failure hold-up time | ≥?50?ms | Nominal output voltage [V] | DC?24?V (SELV) |
Output voltage range | DC?24?V | Default setting | DC?24?V |
Nominal output current I<sub>o nom</sub> | 4.2?A;?3.3?A (< 110 VAC) | Nominal output power | 100W |
Deviation | ≤?1?% | Deviation, dynamic load change 10 … 90 % | ≤?1?% |
Residual ripple | ≤?100?mV (peak-to-peak) | Overload behavior | Constant power (in overload range: 1.05 … 1.35 x Io nom); Shutdown and automatic restart in the event of a short circuit or permanent overload |
Signaling | 1 x LED DC OK (green) | Operation status indicator | Green LED (Uo) |
Power loss P<sub>l</sub> | ≤?0.7?W | Power loss (max.) P<sub>l (max.)</sub> | 15?W (100 VAC / 24 VDC; 4.2 A) |
Efficiency (typ.) | 90?% (230?VAC);?87?% (110 VAC) | Internal fuse | T 3.15 A / 500 VAC |
Backup fusing (required) | An external DC fuse is required for the DC input voltage. | Backup fusing (recommended) | Circuit breaker: 6?A (C characteristic), 10 A (B characteristic) or higher |