Product Model
787-3861/600-000

Selling Points
- 1Space-saving design with one channel for efficient electrical connections.
- 2Reliable overload and short circuit protection ensures safe operation.
- 3Switch-on capacity > 50,000 μF supports high inrush currents.
- 4Adjustable status signal for customizable messaging and monitoring.
- 5DIN Rail mounting for easy integration into industrial settings.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Note | The device is designed for use in SELV circuits. | Isolation voltage (connectors – housing) | DC 1.5?kV |
Protection class | III | Protection type | IP20; per EN 60529 |
Reverse voltage protection | No | Transient suppression (primary) | Suppressor diode (33 V) |
Parallel operation of single channels | Not permitted | Series operation | No |
MTBF | 1,168,394 h | Number of jumper slots | 8 |
Connection technology | Push-in CAGE CLAMP? | WAGO connector | WAGO 857 Series |
Solid conductor | 0.08 … 2.5?mm2?/ 26 … 14?AWG | Fine-stranded conductor | 0.34 … 2.5?mm2?/ 22 … 14?AWG |
Strip length | 9 … 10?mm?/ 0.35 … 0.39?inches | Note (conductor cross-section) | Depending on the output current, use the conductor cross-sections tested and approved by UL:26 … 14 AWG (0.5 A);18 … 14 AWG (6 A) |
Width | 6?mm?/ 0.236?inches | Height | 94 mm / 3.701 inches |
Depth from upper-edge of DIN-rail | 97.8 mm / 3.85 inches | Mounting type | DIN-35 rail |
Fire load | 0.631MJ | Weight | 55.6g |
Ambient temperature (operation) | -25 … +70 °C | Ambient temperature (storage) | -40 … +85 °C |
Relative humidity | 10 … 95?% (no condensation permissible) | Derating | See instruction manual |
Operating altitude | ≤ 2000 m (a.s.l.) | Conformity marking | CE; UKCA |
Standards/specifications | EN 61000-6-2 | ETIM 9.0 | EC001440 |
ETIM 8.0 | EC001440 | ECCN | NO US CLASSIFICATION |
PU (SPU) | 1?pcs | Packaging type | Bag |
Country of origin | IN | Customs tariff number | 85363010900 |
CAS-No. | 11120-22-2 | REACH Candidate List Substance | Diboron trioxide |
RoHS Compliance Status | Compliant,With Exemption | RoHS Exemption | 6(c) |
SCIP notification number (Austria) | 12a75061-6c6c-490d-a64e-5e9a64e31eb3 | SCIP notification number (Belgium) | a199717d-f6d2-4783-bae8-13cb7b66c32f |
SCIP notification number (Bulgaria) | a51532b1-033b-47cb-b814-01e191a61058 | SCIP notification number (Czech Republic) | 4907d0f9-57ab-4763-8161-26f6d7762ea0 |
SCIP notification number (Denmark) | add5826e-f89a-4e57-96a1-41bb9b141bbd | SCIP notification number (Finland) | 9f147a01-9e41-4da5-97e3-c916903c21d4 |
SCIP notification number (France) | 8d3d4298-579a-4fad-86e1-1cf813e41e53 | SCIP notification number (Germany) | 9b585ec8-dfdc-4747-a87b-8d69ceeca1c1 |
SCIP notification number (Hungary) | 38e190ec-f0cf-47a0-8d5d-3c8ffd062909 | SCIP notification number (Italy) | 20049dc2-315e-4a8e-826a-65f3b691caff |
SCIP notification number (Netherlands) | 818c2418-eacb-47ab-9101-acbde01645a8 | SCIP notification number (Poland) | 60136c2f-5531-4ee0-82f0-6c623b1fbb36 |
SCIP notification number (Romania) | c6a6ede4-e322-4847-957d-a3fe52dea868 | SCIP notification number (Sweden) | 63841341-d7eb-40aa-9a88-70dabdf270b0 |
Nominal input voltage [V] | DC?24?V | Input voltage range | DC 18 … 30 V |
Number of Channels | 1 | Nominal output voltage [V] | 1 x DC?24?V |
Output voltage range | DC 18 … 30?V?(Ue? voltage drop) | Voltage drop | ≤?180?mV |
Nominal output current I<sub>o nom</sub> | 1 x 6?A (fixed setting) | Default setting | switched off |
Trip time | 4 ms … 100 s (load-dependent) | Switch-on capacity | >?50000?μF?(see instruction manual) |
Switch-on behavior | Time-delayed channel switching (load-dependent, min. 0 ms/max. 500 ms) | Signaling | 1 x Status LED (green/yellow/red) |
Operation status indicator | Green LED (channel OK) | Remote input | 1 x Control input (15 … 30 VDC (active high); 0 … 5 VDC (active low); max. 0.015 A) |
Power loss P<sub>l</sub> | ≤ 0.4 W (no load) | Efficiency (typ.) | 98?% |
Internal fuse | T 8 A | Overvoltage category | II |
Pollution degree | 2 |
Specifications may be subject to change without notice